2 SYSTEM CONFIGURATION AND AVAILABLE FUNCTIONS

MELSEC-Q

(3) Setting from GX Developer

The following parameters should be set through GX Developer in order to use the Q series C24 mounted to a MELECNET/H remote I/O station.

Each of setting is the same way as when setting the parameters for the Q series C24 mounted to a QCPU station: see Section 4.5 and after.

See the operating manual for GX Developer for how to display each setting screen.

(Parameter setting items for the Q series C24 mounted to a MELECNET/H remote I/O station)

Parameter setting item

Setting

Remarks

I/O Assignment

Set the module mounting information

See Section 4.5.1

Switch setting for I/O and

Set the transmission specification and the

 

communication protocol for communication

See Section 4.5.2

intelligent function module

with the external device

 

 

 

Remote password setting

Perform settings for the remote password.

User's Manual (Application)

Section 3.3.3

 

 

POINT

(1)Connect GX Developer to a MELECNET/H remote I/O station and set the parameters.

(2)Reset the MELECNET/H remote I/O station after changing the setting.

(4)When monitoring/setting with GX Configurator-SC

(a)About the automatic refresh setting

1)When reading/writing data created by the automatic refresh setting using PLC, the read/write operation should be performed by GX Developer. It cannot be performed from GX Configurator-SC.

2)The devices used for the automatic refresh setting must be of the types M, B, D, or W.

POINT

(1)GX Configurator-SC should be connected to a MELECNET/H remote I/O station before the monitoring/setting.

(2)The MELECNET/H remote I/O station should be reset after changing the setting.