APPENDIX

Appendix 9.6 When clearing received data

MELSEC-Q

The following program example uses the receive data clear request area of the buffer memory.

Refer to Section 6.1.4 for received data clear.

(1) Program conditions

The following program clears the received data in the OS area of the QJ71C24N when the receive clear command (X1025) turns ON.

(a) Devices used:

• Receive clear command.........................................................

X1025

• Receive clear processing execution command .....................

M10

• Receive processing flag..........................................................

M11

• Transmission processing flag.................................................

M12

• Receive clear command pulse signal ....................................

M15

• Receive clear acceptance flag ...............................................

M16

• Receive clearing flag...............................................................

M17

• Communication disable flag ...................................................

M18

• Communication enable flag....................................................

M19

• Completion check flag ............................................................

M20

• Receive clear processing execution status acquisition

 

command................................................................................

M21

• Receive clear processing execution status judgment

 

command................................................................................

M22

• Completion device for REMFR/REMTO instruction ..............

M100 to 103

• Normal/abnormal completion flag for REMFR/REMTO

 

instruction................................................................................

M200, M201

• Receive data clear request area information.........................

D0

• Clear request...........................................................................

D1

(b) Intelligent function module switch settings (Refer to Section 4.5.2)

Switch No.

 

Bit

 

Description

 

Setting

Position

Designated value

 

 

value

 

 

 

 

 

 

 

b0

OFF

 

Operation setting

 

Independent

 

 

b1

OFF

 

Data bit

 

7 bits

 

 

b2

OFF

 

Parity bit

 

No

 

 

b3

OFF

Transmission

Even/odd parity

 

Odd

 

Switch 1

b4

OFF

setting

Stop bit

 

1 bit

07C0H

 

b5

OFF

 

Sum check code

 

No

 

 

b6

ON

 

Write during RUN

 

Enabled

 

 

b7

ON

 

Setting modifications

 

Enabled

 

 

b8 to b15

Communication rate setting

 

19200bps

 

Switch 2

 

Communication protocol setting

 

Non-procedure protocol

0006H

Switch 5

 

Station number setting

 

 

Station 0

0000H

(c) Buffer memory settings used in this example

Address Decimal (Hexadecimal)

 

Name

Setting

CH1

 

value

 

 

168 (A8H)

Receive data clear request

 

0, 1

App. - 41

App. - 41