3 SPECIFICATIONS
Address |
|
|
|
|
|
|
|
| Initial | Applicable | Registration | Reference | |||||
Decimal (Hex) | Application |
|
|
|
| Name |
| protocol |
| allowed/not | |||||||
|
|
|
|
| value |
| section | ||||||||||
CH1 | CH2 |
|
|
|
|
|
|
|
| MC |
| Non |
| Bi | allowed | ||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
8256 | 8512 |
| Cycle time units designation |
|
|
| 2 |
|
|
|
|
|
|
| |||
(2040H) | (2140H) |
| 0: 100 ms | 1: s |
| 2: min |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| ||||||||
8257 | 8513 |
| Cycle time designation |
|
|
| 5H |
|
|
|
|
|
|
| |||
| 0H |
|
| : No designation |
|
|
|
|
|
|
|
|
| ||||
(2041H) | (2141H) |
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 1H to FFFFH: PLC CPU monitoring cycle time |
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
8258 | 8514 |
| PLC CPU monitoring function designation |
|
|
|
|
|
|
|
|
| |||||
| 0: Do not use the function. |
| 1: Fixed cycle transmission | 0 |
|
|
|
|
|
|
| ||||||
(2042H) | (2142H) |
|
|
|
|
|
|
|
|
| |||||||
| 2: Condition agreement transmission |
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
| PLC CPU monitoring transmission measure designation |
|
|
|
|
|
|
|
| ||||||
8259 | 8515 | For designation | (for fixed cycle transmission) |
|
|
|
|
|
|
|
|
|
| Chapter 2 | |||
(2043H) | (2143H) | 0: Data transmission (device data and CPU status data) |
|
|
|
|
|
|
| ||||||||
|
| of PLC CPU | 1: Notification |
|
|
|
|
| R |
| — | Allowed | of User's | ||||
|
| monitoring | Transmission pointer designation (For fixed cycle transmission and |
|
|
| Manual | ||||||||||
|
|
|
|
|
|
|
|
| |||||||||
|
| function | data transmission) |
|
|
|
|
|
|
|
|
|
| (Application) | |||
8260 | 8516 |
| 1 to 100: Output head point (send from the nth) |
|
|
|
|
|
|
|
|
| |||||
(2044H) | (2144H) |
| Send the user frames designated in the following transmission | 0 |
|
|
|
|
|
|
| ||||||
|
|
| frame No. designation areas from the designated pointer position. |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
| (addresses: CH1 side = BAH to 11DH, CH2 side = 15AH to 1BDH) |
|
|
|
|
|
|
|
| ||||||
8261 | 8517 |
| Output count designation (for fixed cycle transmission and data |
|
|
|
|
|
|
|
| ||||||
| transmission) |
|
|
|
|
|
|
|
|
|
|
|
| ||||
(2045H) | (2145H) |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| 1 to 100:Output count (designate the number of frame transmissions.) |
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
8262 | 8518 |
| Data No. for connection designation (for fixed cycle transmission |
|
|
|
|
|
|
|
| ||||||
| and notification) |
|
|
|
|
|
|
|
|
|
|
| |||||
(2046H) | (2146H) |
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 0BB8H to 0BD5H, 8001H to 801FH: Data No. for connection |
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
8263 to | 8519 to |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8268 | 8524 | Use prohibited | System area |
|
|
|
|
|
|
|
|
|
| — |
| ||
(2047H to | (2147H to |
|
|
|
|
|
|
|
|
|
|
| |||||
204CH) | 2149H) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8269 | 8225 |
| Number of registered word blocks designation |
|
|
|
|
|
|
|
|
| |||||
| 0 | : No designation |
|
| It is possible to |
|
|
|
|
|
|
|
| ||||
(204DH) | (214DH) |
|
|
|
|
|
|
|
|
|
|
| |||||
| 1 to 10: Number of blocks of word devices | designate a |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
8270 | 8226 |
| Number of registered bit blocks designation | maximum of 10 |
|
|
|
|
|
|
|
| |||||
| 0 | : No designation |
|
| blocks in total. |
|
|
|
|
|
|
|
| ||||
(204EH) | (214EH) |
|
|
|
|
|
|
|
|
|
|
| |||||
| 1 to 10: Number of blocks of bit devices |
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
8271 | 8527 |
| PLC CPU abnormal monitoring designation |
|
|
|
|
|
|
|
|
| |||||
(204FH) | (214FH) |
| 0: Do not monitor. |
| 1: Monitor. |
|
|
|
|
|
|
|
|
| |||
8272 | 8528 |
|
|
| Monitoring device designation |
|
|
|
|
|
|
|
|
| |||
(2050H) | (2150H) |
|
|
|
| 90H to CCH: Device code |
|
|
|
|
|
|
|
|
| ||
8273 to | 8529 to |
|
|
| Head device No. designation |
|
|
|
|
|
|
|
|
| |||
8274 | 8530 |
|
|
|
| 0 or more: Head device No. |
|
|
|
|
|
|
|
|
| ||
(2051H to | (2151H to |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2052H) | 2152H) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8275 | 8531 |
|
|
| Read point designation |
|
|
|
|
|
|
|
|
|
| ||
(2053H) | (2153H) |
|
|
|
| 1 or more: Number to read points |
|
|
|
|
|
|
|
|
| ||
8276 | 8532 |
|
|
| Monitoring condition designation (judgment condition |
|
|
|
|
|
|
|
| ||||
For designation |
|
| designation) |
|
|
|
|
|
|
|
|
|
|
| |||
(2054H) | (2154H) |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| of PLC CPU |
|
|
| 1 or more: Monitoring condition |
| 0 |
| R |
| — |
|
| |||
8277 | 8533 | monitoring |
|
| Monitoring condition value designation |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| ||||||||
function | No. 1 |
|
| At bit device | 0: OFF | 1: ON |
|
|
|
|
|
|
|
| Chapter 2 | ||
(2055H) | (2155H) |
|
|
| At word device |
| H |
|
|
|
|
|
|
|
| of User's | |
|
|
| block |
|
| 0 to FFFF : Monitoring condition value |
|
|
|
|
|
| Allowed | ||||
|
|
|
| Transmission pointer designation (for condition |
|
|
|
|
|
| Manual | ||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
| monitoring | agreement transmission and data transmission) |
|
|
|
|
|
|
| (Application) | |||||
|
|
| device |
| 1 to 100: Output head point (send from nth) |
|
|
|
|
|
|
|
| ||||
8278 | 8534 |
|
|
|
| Send the user frames designated in the following |
|
|
|
|
|
|
|
| |||
(2056H) | (2156H) |
|
|
|
| transmission frame No. designation areas from the |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| designated pointer position. |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| (address: CH1 side = BAH to 11DH, CH2 side = 15AH |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| to 1BDH) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Output count designation (for condition agreement |
|
|
|
|
|
|
|
| ||||
8279 | 8535 |
|
|
| transmission and data transmission) |
|
|
|
|
|
|
|
|
| |||
(2057H) | (2157H) |
|
|
|
| 1 to 100: Output count (designate the number |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| of frame transmissions) |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| Data No. for connection designation (for condition |
|
|
|
|
|
|
|
| ||||
8280 | 8536 |
|
|
| agreement transmission and notification) |
|
|
|
|
|
|
|
|
| |||
(2058H) | (2158H) |
|
|
|
| 0BB8H to 0BD5H, 8001H to 801FH: Data No. for |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| connection |
|
|
|
|
|
|
|
|
8281 to | 8537 to | For designation | Block |
|
|
|
|
|
|
|
|
|
|
|
|
| |
monitoring | The structure of each area is the same as the first block monitoring device area |
|
| ||||||||||||||
8361 | 8617 | of PLC CPU |
|
| |||||||||||||
(2059H to | (2159H to | monitoring | devices | See *2 for the details of each area. |
|
|
|
|
|
|
|
|
| ||||
20A9H) | 21A9H) | function | No. 2 to |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8362 to | 8618 to |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8421 | 8677 | Use prohibited | System area |
|
|
|
|
|
|
|
|
|
| — |
| ||
(20AAHto | (21AAHto |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20E5H) | 21E5H) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 - 28 | 3 - 28 |