10 TROUBLESHOOTING

10.2 Error Code Tables

MELSEC-Q

The following shows the error codes, error contents, and corrective action for errors that are generated during communication between the Q series C24 and an external device.

The signal name in the following table indicates the CH side LED on status or communication error status that is stored into buffer memory address 201H/202H when an error occurs.

The CH side LED on status and communication error status can be confirmed by GX Developer's System monitor or GX Configurator-SC. (Refer to Section 10.1.1.)

For errors without a corresponding signal name entered to errors generated with the MC protocol communication, “NAK” comes on.

10.2.1 Error code table

The following shows the error codes, error contents, and corrective action for errors generated during communication using MC protocol (excluding A compatible 1C frame), non procedure protocol, and bidirectional protocol.

("" in the table is the error code when the target CPU is not a Q/QnACPU.)

Error code

 

 

 

Signal

 

 

 

Protocol

 

Error

 

 

 

 

 

Non

 

(Hexa-

 

Error Contents

 

Corrective action

 

Bidire-

 

name

 

MC

Proce-

decimal)

 

 

 

 

 

 

 

dure

ctional

 

 

 

 

 

 

 

 

 

3E8H

 

 

 

 

See Troubleshooting of the

 

 

 

 

 

 

 

 

QCPU (Q mode) maintenance

 

 

 

to

 

(Error detected by the CPU)

 

 

 

 

 

 

and inspection user's manual

 

 

 

3FFFH

 

 

 

 

 

 

 

 

 

 

 

 

 

and take corrective action.

 

 

 

 

 

 

 

 

 

 

 

 

4000H

 

 

 

 

See Appendix of the QCPU (Q

 

 

 

 

 

 

 

 

mode) maintenance and

 

 

 

to

 

(Error detected by the CPU)

 

inspection user's manual

 

 

 

4FFFH

 

 

 

 

 

(details) and take corrective

 

 

 

 

 

 

 

 

 

action.

 

 

 

7101H

System error

The OS of the Q series C24 detected some error.

(

1)

 

 

 

7102H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Make the watchdog timer (timer

 

 

 

 

 

 

 

 

 

1) time longer.

 

 

 

7103H

PLC access error

Cannot communicate with the Q series C24 CPU.

C/N

Check if the CPU can

 

 

 

 

 

 

 

 

 

communicate in communication

 

 

 

 

 

 

 

 

 

protocol No. "F".

 

 

 

7104H

 

 

 

 

 

 

 

 

 

to

System error

The OS of the Q series C24 detected some error.

(

1)

 

 

 

7116H

 

 

 

 

 

 

 

 

 

 

 

Number of request points exceeds the range for the

 

 

 

 

 

 

 

 

 

command.

 

 

 

 

 

 

 

 

A word device was designated in a bit units

 

Check and correct the external

 

 

 

7140H

Request data error

 

command.

PRO

 

device transmit message and

 

 

 

 

 

The last device No. exceeds the range.

 

 

restart data communications.

 

 

 

 

 

 

Given device last No. > Designated head device

 

 

 

 

 

 

 

 

 

No. + Designated number of points

 

 

 

 

 

 

7141H

System error

The OS of the Q series C24 detected some error.

(

1)

 

 

 

 

 

A device that cannot be designated by the given

 

Check and correct the external

 

 

 

7142H

Device name error

PRO

 

device transmit message and

 

 

 

 

 

 

command was designated.

 

 

restart data communications.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check and correct the external

 

 

 

7143H

Device No. error

The head device No. is out of range.

PRO

 

device transmit message and

 

 

 

 

 

 

 

 

 

restart data communications.

 

 

 

7144H

Monitor data write

Monitoring was requested before the device to be

PRO

Write the device to be monitored

 

 

 

 

error

 

monitored was written.

 

 

before issuing a monitor request.

 

 

 

7145H

Monitor PLC No.

The written PLC No. and PLC No. in the monitor

C/N

Rewrite the monitor data.

 

 

 

error

 

request are different.

 

 

 

 

 

 

 

 

 

 

 

7146H

Monitor CPU model

The written CPU model name and the CPU monitor

C/N

Rewrite the monitor data.

 

 

 

name error

 

name in the monitor request are different.

 

 

 

 

 

 

 

 

 

 

 

7147H

Written number of

The written number of monitoring points exceeds

PRO

Check and correct the external

 

 

 

monitoring points

 

the designated range.

 

device transmit message and

 

 

 

 

overrun error

 

 

 

restart data communications.

 

 

 

 

 

 

 

 

 

 

 

10 - 15

10 - 15