3SPECIFICATIONS
POINT
(1)When the external device and the Q series C24 connected in n:1 and m:n configurations
When the send signal of each device is connected as shown below, if the "Output control input" is turned ON at two or more devices, the relevant devices output (send) data at the same time.
For the external device to transfer data normally,
•"Output control input" must be turned ON only when sending data.
•"Output control input" must be turned OFF when not sending data.
External device or converter
SDA
Send data
SDB
Output control input RDA
Receive
dataRDB
|
|
|
| SDA |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Send data |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| SDB |
|
|
|
|
|
| Q series C24 | ||
|
|
|
| RDA | Output control input | ||||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| Receive |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| RDB |
|
|
|
|
|
|
| data |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| SDA |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Send data |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| SDB |
|
|
|
|
|
| Q series C24 | ||
|
|
|
| RDA Output control input | |||||||||
|
|
|
|
|
|
|
|
|
|
|
| Receive |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| RDB |
|
|
|
|
|
| data |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(2)When the Q series C24 is used, if operation of the two interfaces is linked (see Section 4.5.2 (2)), the time to send one character becomes the Q series C24 H/W gate OFF time.
(The Q series C24 turns OFF the gate after the
3 - 10 | 3 - 10 |