10 TROUBLESHOOTING
10.3.8 Troubleshooting when communication error "PRO." generates
Symptom | Cause |
|
| Corrective action | MC |
| • Communications were | • Check the Q series C24 communication |
| ||
| performed with a control | protocol setting and the message from the |
| ||
| procedure different from |
| |||
| external device and match the settings, or |
| |||
| the Q series C24 |
| |||
| correct the message and restart data |
| |||
| communication protocol |
| |||
| communications. |
| |||
| setting. |
| |||
| • Some of the data are |
|
|
|
|
| different from the control |
|
|
|
|
| procedure. |
|
|
|
|
| • Designated command |
|
|
|
|
| does not exist. |
|
|
|
|
| • The device No. |
|
|
|
|
| designation is not the |
|
|
|
|
| character count |
|
|
|
|
| corresponding to the |
|
|
|
|
| command. | • Check and correct the external device message |
| ||
| • The characters in the |
| |||
| message include a data | and restart data communications. |
| ||
| other than the "A to Z", | Note | Only the data "0 to 9" and "A to F" can be |
| |
| "0 to 9", " ", and | • |
| ||
| control data. |
| handled as character area data during |
| |
|
| communications using an MC protocol (ASCII |
| ||
• Communication error |
|
|
| ||
|
| mode). Therefore, when transmitting a |
| ||
signal "PRO" turned on. |
|
|
| ||
|
| character string as data, convert the ASCII code |
| ||
|
|
| of each character string to |
| |
|
| Examples) |
| ||
|
| • | Transmitting the character "G" |
| |
|
|
| The ASCII code for the character "G" is 47H |
| |
|
|
| and is transmitted as the two bytes 34 H, 37H. |
| |
|
| • | Transmitting the character "A" |
| |
|
|
| The ASCII code for "A" is 41H and is |
| |
|
|
| transmitted as the two bytes 34H, 31H. |
| |
|
|
| If the ASCII code 41H for the character "A" is |
| |
|
|
| transmitted unchanged, the Q series C24 |
| |
|
|
|
| ||
|
|
| (10) and pass it to the PLC CPU. |
| |
| • A device No. outside the | • When designating a device, check "Device |
| ||
| designated range was | setting" of the parameters written to the CPU |
| ||
| designated. | and correct it to a device No. within the |
| ||
|
| designated range and restart data |
| ||
|
| communications. |
| ||
| • A remote RUN/STOP | • Check if remote STOP is applied from another |
| ||
| request was issued | module and restart data communications. |
| ||
| while remote STOP was |
| |||
|
|
|
|
| |
| applied from another |
|
|
|
|
| module. |
|
|
|
|
Bidirectional Non procedure