10 TROUBLESHOOTING
Error code |
|
|
|
|
|
|
| Protocol |
|
Error |
| Error Contents | Signal |
| Corrective action |
| Non |
| |
(Hexa- |
|
|
| Bidire- | |||||
| name |
| MC | Proce- | |||||
decimal) |
|
|
|
|
| ctional | |||
|
|
|
|
|
|
|
| dure |
|
|
| • | A nonexistent device was designated. |
| • | Check and correct the external |
|
|
|
716FH | Device error | • | Device that cannot be specified by the | PRO |
| device transmit message and |
|
|
|
|
|
| corresponding command was designated. |
|
| restart data communications. |
|
|
|
7170H |
| • | Number of access points exceeded the range. | PRO |
|
|
|
|
|
| A compatible 1C |
|
|
| • Check and correct the external |
|
|
| |
|
|
|
|
|
|
| |||
7171H | • | A device that cannot be designated was designated. | PRO |
| device transmit message and |
|
|
| |
frame error |
|
|
|
| |||||
|
|
|
|
| restart data communications. |
|
|
| |
7172H |
| • | Written number of monitoring points is incorrect. For | PRO |
|
|
|
| |
|
|
|
|
|
| ||||
|
| example, [0] was designated. |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
| Monitor data write | • | Monitor data was written for a CPU other than a |
| • Write the monitor data and use |
|
|
| |
7173H | PRO |
| the A compatible 1C frame to a |
|
|
| |||
error |
| Q/QnACPU using QnA compatible 2C/3C/4C frame. |
|
|
|
| |||
|
|
|
| CPU other than a Q/QnACPU. |
|
|
| ||
|
|
|
|
|
|
|
|
| |
7E00H |
|
|
|
|
|
|
|
|
|
to | System error | • | The OS of the Q series C24 detected some error. | — | ( | 1) |
|
|
|
7E05H |
|
|
|
|
|
|
|
|
|
| Buffer memory | • | Transmit/receive buffer memory addresses are in |
| • Change the buffer memory |
|
|
| |
7E06H | address setting | |
| addresses so that they are outside |
|
|
| ||
| the special applications area. |
|
|
|
| ||||
| error |
|
|
| the special applications area. |
|
|
| |
|
|
|
|
|
|
|
| ||
7E07H |
|
|
|
|
|
|
|
|
|
to | System error | • | The OS of the Q series C24 detected some error. | — | ( | 1) |
|
|
|
7E0AH |
|
|
|
|
|
|
|
|
|
|
| • | A nonexistent command or subcommand was |
| • Check and correct the external |
|
|
| |
7E40H | Command error | PRO |
| device transmit message and |
|
|
| ||
| designated. |
|
|
|
| ||||
|
|
|
|
| restart data communications. |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
| • | A data length exceeding the number of points that |
| • | Check and correct the external |
|
|
|
7E41H | Data length error |
| can communicate during random read/write was | PRO |
| device transmit message and |
|
|
|
|
|
| designated. |
|
| restart data communications. |
|
|
|
|
| • | Number of requested points exceeds the range for |
| • Check and correct the external |
|
|
| |
7E42H | Error count error | PRO |
| device transmit message and |
|
|
| ||
| the command. |
|
|
|
| ||||
|
|
|
|
| restart data communications. |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
| • | A nonexistent device was designated. |
| • | Check and correct the external |
|
|
|
7E43H | Device error | • | Device that cannot be specified by the | PRO |
| device transmit message and |
|
|
|
|
|
| corresponding command was designated. |
|
| restart data communications. |
|
|
|
|
|
|
|
| • Make the timer 1 monitoring |
|
|
| |
7E44H | Timer 1 | • | A response message was not returned within the | C/N |
| time longer. |
|
|
|
• | When accessing another |
|
|
| |||||
error |
| response monitoring time (timer 1) monitoring time. |
|
|
| ||||
|
|
|
| station's CPU, check if the |
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| routing parameters match. |
|
|
|
7E46H | System error | • | The OS of the Q series C24 detected some error. | — | ( | 1) |
|
|
|
|
|
|
|
| • Do not issue continuous |
|
|
| |
|
|
|
|
|
| requests from the external |
|
|
|
7E47H | Continuous request | • | The next request was received before a response | PRO |
| device. |
|
|
|
error |
| message was returned for the preceding request. | • | Set the timer 1 monitoring time |
|
|
| ||
|
|
|
|
|
| to the external device |
|
|
|
|
|
|
|
|
| time. |
|
|
|
7E48H |
|
|
|
|
|
|
|
|
|
to | System error | • | The OS of the Q series C24 detected some error. | — | ( | 1) |
|
|
|
7E4CH |
|
|
|
|
|
|
|
|
|
|
|
|
|
| • | Make arrangements between |
|
|
|
| Error during data | • | Mode switching was executed during data | CHn |
| the target device and PLC CPU |
|
|
|
7E4DH |
| so that mode switching is not |
|
|
| ||||
transmission |
| transmission. | ERR. |
|
|
|
| ||
|
|
| executed during data |
|
|
| |||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| transmission. |
|
|
|
7E4EH | System error | • | The OS of the Q series C24 detected some error. | — | ( | 1) |
|
|
|
| Device point count |
|
|
| • Check and correct the external |
|
|
| |
7E4FH | • | Access point count is incorrect. | PRO |
| device transmit message and |
|
|
| |
| error |
|
|
|
| restart data communications. |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| • Check and correct the external |
|
|
| |
7E50H | User frame No. | • | A user frame No. outside the range was designated. | PRO |
| device transmit message and |
|
|
|
designation error |
| restart data communications. |
|
|
| ||||
|
|
|
|
|
|
|
| ||
|
|
|
|
| • Recheck the frame No.. |
|
|
| |
|
|
|
|
| • Write the frame beforehand. |
|
|
| |
7E51H | Unwritten user | • | An unwritten user frame No. was designated. | PRO | • | Change the frame No. and |
|
|
|
| frame error |
|
|
|
| restart data communications. |
|
|
|
|
|
|
|
| • Recheck the frame No.. |
|
|
|
10 - 17 | 10 - 17 |