10 TROUBLESHOOTING

MELSEC-Q

Error code

 

 

 

 

 

 

 

Protocol

 

Error

 

 

Signal

 

 

 

Non

 

(Hexa-

 

Error Contents

 

Corrective action

 

Bidire-

 

name

 

MC

Proce-

decimal)

 

 

 

 

 

ctional

 

 

 

 

 

 

 

 

dure

 

 

 

 

 

 

Change the write destination to

 

 

 

7E52H

User frame

A written frame No. overwrite request was issued.

PRO

 

an unwritten frame No.

 

 

 

overwrite error

When overwriting, delete the

 

 

 

 

 

 

 

 

 

given No. beforehand.

 

 

 

 

 

A nonexistent command was designated in a

 

Check and correct the external

 

 

 

 

User frame access

 

subcommand.

 

 

 

 

7E53H

 

PRO

 

device transmit message and

 

 

 

data error

Byte count exceeding the number of bytes that can

 

 

 

 

 

 

 

restart data communications.

 

 

 

 

 

 

be requested was designated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flash ROM write allow/prohibit designation from GX

 

Set to ON at GX Configurator-

 

 

 

 

Modification

 

Configurator-SC is set to OFF.

 

 

 

 

7E54H

 

PRO

 

SC.

 

 

 

allowed error

At the switch setting on GX Developer, modification

 

 

 

 

 

 

Set to ON at GX Developer.

 

 

 

 

 

 

allowed switch was set to OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User frame data

 

 

 

Check and correct the external

 

 

 

7E55H

There is an error in the user frame variable data.

PRO

 

device transmit message and

 

 

 

error

 

 

 

 

 

 

 

 

 

restart data communications.

 

 

 

 

 

 

 

 

 

 

 

 

7E56H

System error

The OS of the Q series C24 detected some error.

(

1)

 

 

 

 

Flash ROM write

 

 

 

Re-execute the write operation.

 

 

 

7E57H

Cannot write to Flash ROM normally.

PRO

 

If the error is generated again,

 

 

 

error

 

 

 

 

 

 

 

 

 

replace the module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check and correct the contents

 

 

 

 

 

There was an error in the mode No. or transmission

 

 

of the external device transmit

 

 

 

7E58H

Mode modification

PRO

 

message and restart data

 

 

 

error

 

specification designated contents when changing

 

communications.

 

 

 

 

 

the mode.

 

 

 

 

 

 

 

 

 

Recheck the switch setting on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the Q series C24.

 

 

 

 

 

 

 

 

Review the program.

 

 

 

 

Flash ROM write

 

 

 

Rewrite the flash ROM area

 

 

 

7E59H

count over limit

Flash ROM written 1,000 times

 

(address: 2401H) of the buffer

 

 

 

 

error

 

 

 

 

memory to 0 and restart data

 

 

 

 

 

 

 

 

 

communications.

 

 

 

 

I/O number error

 

 

 

Correct the I/O number of the

 

 

 

7E5FH

on requested

I/O number of requested module is incorrect.

 

 

 

 

module to which data is sent.

 

 

 

 

module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7E60H

Device monitoring

PLC CPU monitoring registration was performed

Cancel the PLC CPU monitoring

 

 

 

duplicate

 

twice.

 

and perform the PLC CPU

 

 

 

 

registration error

 

 

 

monitoring registration again.

 

 

 

 

 

 

 

 

 

 

 

7E61H

Cycle time units

Setting value of cycle time units is out of range.

Correct the setting value of the

 

 

 

range error

 

cycle time units.

 

 

 

 

 

 

 

 

 

 

 

 

PLC CPU

Setting value of PLC CPU monitoring function is out

 

Correct the setting value of the

 

 

 

7E62H

monitoring function

 

 

 

 

error

 

of range.

 

 

PLC CPU monitoring function.

 

 

 

 

 

 

 

 

 

 

 

 

 

Transmission

Setting of transmission measure of the PLC CPU

 

Correct the setting value of the

 

 

 

7E63H

measure setting

 

 

 

 

monitoring is incorrect.

 

transmission measure.

 

 

 

 

error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7E64H

Registration point

Registration point (word/bit) is out of range.

Correct the setting value of the

 

 

 

range error

 

registration point (word/byte)

 

 

 

 

 

 

 

 

 

 

 

7E65H

PLC CPU abnormal

Setting value of the PLC CPU abnormal monitoring

Correct the setting value of the

 

 

 

monitoring number

 

is out of range.

 

PLC CPU abnormal monitoring.

 

 

 

 

error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Monitoring

Setting value of transmission condition is out of

 

Correct the setting value of the

 

 

 

7E66H

condition error of

 

 

 

 

range.

 

transmission condition.

 

 

 

 

monitoring device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU abnormal

Setting value (fixed value) of CPU abnormal

 

Correct the setting value (fixed

 

 

 

7E67H

monitoring setting

 

value) of the CPU abnormal

 

 

 

 

monitoring is out of range.

 

 

 

 

 

value error

 

 

 

monitoring.

 

 

 

 

 

 

 

 

 

 

 

 

Transmission

 

 

 

Correct the setting value of the

 

 

 

7E68H

condition range

Setting value of transmission condition (condition

 

transmission condition

 

 

 

error of monitoring

 

agreement transmission) is out of range.

 

(condition agreement

 

 

 

 

 

 

 

 

 

 

 

device

 

 

 

 

transmission).

 

 

 

 

CPU abnormal

Setting value (fixed value) of CPU abnormal

 

Correct the setting value (fixed

 

 

 

7E69H

monitoring setting

 

value) of the CPU abnormal

 

 

 

 

monitoring is out of range.

 

 

 

 

 

value error

 

 

 

monitoring.

 

 

 

 

 

 

 

 

 

 

 

10 - 18