10 TROUBLESHOOTING
Error code |
|
|
|
|
|
|
| Protocol |
|
Error |
|
| Signal |
|
|
| Non |
| |
(Hexa- |
| Error Contents |
| Corrective action |
| Bidire- | |||
| name |
| MC | Proce- | |||||
decimal) |
|
|
|
|
| ctional | |||
|
|
|
|
|
|
|
| dure |
|
|
|
|
|
| • Change the write destination to |
|
|
| |
7E52H | User frame | • | A written frame No. overwrite request was issued. | PRO |
| an unwritten frame No. |
|
|
|
overwrite error | • | When overwriting, delete the |
|
|
| ||||
|
|
|
|
|
| given No. beforehand. |
|
|
|
|
| • A nonexistent command was designated in a |
| • Check and correct the external |
|
|
| ||
| User frame access |
| subcommand. |
|
|
|
| ||
7E53H |
| PRO |
| device transmit message and |
|
|
| ||
data error | • | Byte count exceeding the number of bytes that can |
|
|
|
| |||
|
|
| restart data communications. |
|
|
| |||
|
|
| be requested was designated. |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
| • Flash ROM write allow/prohibit designation from GX |
| • Set to ON at GX Configurator- |
|
|
| ||
| Modification |
|
|
|
|
| |||
7E54H |
| PRO |
| SC. |
|
|
| ||
allowed error | • | At the switch setting on GX Developer, modification |
|
|
|
| |||
|
| • Set to ON at GX Developer. |
|
|
| ||||
|
|
| allowed switch was set to OFF. |
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
| User frame data |
|
|
| • Check and correct the external |
|
|
| |
7E55H | • | There is an error in the user frame variable data. | PRO |
| device transmit message and |
|
|
| |
error |
|
|
|
| |||||
|
|
|
|
| restart data communications. |
|
|
| |
|
|
|
|
|
|
|
|
| |
7E56H | System error | • | The OS of the Q series C24 detected some error. | — | ( | 1) |
|
|
|
| Flash ROM write |
|
|
| • |
|
|
| |
7E57H | • | Cannot write to Flash ROM normally. | PRO |
| If the error is generated again, |
|
|
| |
error |
|
|
|
| |||||
|
|
|
|
| replace the module. |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
|
| • Check and correct the contents |
|
|
| |
|
| • | There was an error in the mode No. or transmission |
|
| of the external device transmit |
|
|
|
7E58H | Mode modification | PRO |
| message and restart data |
|
|
| ||
error |
| specification designated contents when changing |
| communications. |
|
|
| ||
|
| the mode. |
|
|
|
|
| ||
|
|
|
| • Recheck the switch setting on |
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| the Q series C24. |
|
|
|
|
|
|
|
| • | Review the program. |
|
|
|
| Flash ROM write |
|
|
| • Rewrite the flash ROM area |
|
|
| |
7E59H | count over limit | • | Flash ROM written 1,000 times | — |
| (address: 2401H) of the buffer |
|
|
|
| error |
|
|
|
| memory to 0 and restart data |
|
|
|
|
|
|
|
|
| communications. |
|
|
|
| I/O number error |
|
|
| • Correct the I/O number of the |
|
|
| |
7E5FH | on requested | • | I/O number of requested module is incorrect. | — |
|
|
| ||
| module to which data is sent. |
|
|
| |||||
| module |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
7E60H | Device monitoring | • | PLC CPU monitoring registration was performed | — | • | Cancel the PLC CPU monitoring |
|
|
|
duplicate |
| twice. |
| and perform the PLC CPU |
|
|
| ||
| registration error |
|
|
| monitoring registration again. |
|
|
| |
|
|
|
|
|
|
|
| ||
7E61H | Cycle time units | • | Setting value of cycle time units is out of range. | — | • Correct the setting value of the |
|
|
| |
range error |
| cycle time units. |
|
|
| ||||
|
|
|
|
|
|
|
| ||
| PLC CPU | • | Setting value of PLC CPU monitoring function is out |
| • | Correct the setting value of the |
|
|
|
7E62H | monitoring function | — |
|
|
| ||||
| error |
| of range. |
|
| PLC CPU monitoring function. |
|
|
|
|
|
|
|
|
|
|
|
| |
| Transmission | • | Setting of transmission measure of the PLC CPU |
| • | Correct the setting value of the |
|
|
|
7E63H | measure setting | — |
|
|
| ||||
| monitoring is incorrect. |
| transmission measure. |
|
|
| |||
| error |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
7E64H | Registration point | • | Registration point (word/bit) is out of range. | — | • Correct the setting value of the |
|
|
| |
range error |
| registration point (word/byte) |
|
|
| ||||
|
|
|
|
|
|
|
| ||
7E65H | PLC CPU abnormal | • | Setting value of the PLC CPU abnormal monitoring | — | • | Correct the setting value of the |
|
|
|
monitoring number |
| is out of range. |
| PLC CPU abnormal monitoring. |
|
|
| ||
| error |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
| Monitoring | • | Setting value of transmission condition is out of |
| • | Correct the setting value of the |
|
|
|
7E66H | condition error of | — |
|
|
| ||||
| range. |
| transmission condition. |
|
|
| |||
| monitoring device |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
| CPU abnormal | • | Setting value (fixed value) of CPU abnormal |
| • Correct the setting value (fixed |
|
|
| |
7E67H | monitoring setting | — |
| value) of the CPU abnormal |
|
|
| ||
| monitoring is out of range. |
|
|
|
| ||||
| value error |
|
|
| monitoring. |
|
|
| |
|
|
|
|
|
|
|
| ||
| Transmission |
|
|
| • Correct the setting value of the |
|
|
| |
7E68H | condition range | • | Setting value of transmission condition (condition | — |
| transmission condition |
|
|
|
error of monitoring |
| agreement transmission) is out of range. |
| (condition agreement |
|
|
| ||
|
|
|
|
|
|
| |||
| device |
|
|
|
| transmission). |
|
|
|
| CPU abnormal | • | Setting value (fixed value) of CPU abnormal |
| • Correct the setting value (fixed |
|
|
| |
7E69H | monitoring setting | — |
| value) of the CPU abnormal |
|
|
| ||
| monitoring is out of range. |
|
|
|
| ||||
| value error |
|
|
| monitoring. |
|
|
| |
|
|
|
|
|
|
|
|
10 - 18 | 10 - 18 |