10 TROUBLESHOOTING

MELSEC-Q

Error code

 

 

 

 

 

 

 

Protocol

 

Error

 

 

Signal

 

 

 

Non

 

(Hexa-

 

Error Contents

 

Corrective action

 

Bidire-

 

name

 

MC

Proce-

decimal)

 

 

 

 

 

ctional

 

 

 

 

 

 

 

 

dure

 

7FC9H

 

 

 

 

 

 

 

 

 

to

System error

 

The OS of the Q series C24 detected some error.

(

1)

 

 

 

7FCFH

 

 

 

 

 

 

 

 

 

7FE6H

 

 

Remote passwords do not match.

Check the remote password and

 

 

 

 

 

 

communicate again.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A remote password processing

 

 

 

 

 

 

The remote password is not registered.

 

 

command is not necessary

 

 

 

 

 

 

The remote password processing command was

 

 

when a remote password is not

 

 

 

 

 

 

 

 

registered.

 

 

 

 

 

 

received on the interface side where the modem

 

 

 

 

 

 

 

 

CHn

Perform a remote password

 

 

 

7FE7H

 

 

function is not used.

 

 

 

Processing

 

ERR.

 

unlock processing through GX

 

 

 

 

 

The GX Developer connection is selected in the

 

 

 

 

 

disabled

 

 

 

Developer. Alternatively, change

 

 

 

 

 

communication protocol setting on the

 

 

 

 

 

 

 

 

 

 

the communication protocol

 

 

 

 

 

 

corresponding CH.

 

 

setting of the corresponding CH

 

 

 

 

 

 

 

 

 

to the MC protocol.

 

 

 

 

 

 

The number of remote password disagreements

CHn

Clear the storage area of the

 

 

 

 

 

 

 

cumulative number of abnormal

 

 

 

7FE8H

 

 

exceeded the value designated at the address

 

 

 

 

 

 

ERR.

 

completions of unlock processing

 

 

 

 

 

 

200D H.

 

 

 

 

 

 

 

 

 

(address: 22FCH) to 0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

There is an error in the switch setting by the GX

CHn

Write CPU to the parameter and

 

 

 

7FEFH

Switch setting error

 

reboot after correcting the

 

 

 

 

 

 

Developer

ERR.

 

setting value for the switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

Dedicated

 

 

 

 

 

 

 

 

7FF0H

instructions

 

Executed dedicated instructions simultaneously.

Do not use dedicated

 

 

 

simultaneous

 

 

instructions simultaneously.

 

 

 

 

 

 

 

 

 

 

 

 

execution error

 

 

 

 

 

 

 

 

7FF1H

Control data error

 

Setting value is incorrect.

Correct the setting value in the

 

 

 

 

Setting value is out of range.

 

control data.

 

 

 

 

 

 

 

 

 

 

 

 

Communication

 

Instruction cannot be executed with the current

 

Correct the setting value of the

 

 

 

7FF2H

protocol setting

 

 

 

 

 

communication protocol.

 

communication protocol.

 

 

 

 

error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7FF3H

 

 

 

 

 

 

 

 

 

to

System error

 

The OS of the Q series C24 detected some error.

(

1)

 

 

 

7FF4H

 

 

 

 

 

 

 

 

 

 

Processing

 

 

 

 

 

 

 

 

 

canceled due to

 

The processing was canceled due to mode

 

Do not execute mode

 

 

 

 

mode

 

 

 

 

 

7FF5H

 

switching or receive data clear executed during the

 

switching/receive data clear

 

 

 

switching/transmiss

 

 

 

 

 

processing.

 

 

during any processing.

 

 

 

 

ion sequence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

initialization

 

 

 

 

 

 

 

 

 

 

 

 

 

Multiple external devices must

 

 

 

7FF7H

Simultaneous

 

Multiple external devices accessed a remote station

 

not access a remote station on

 

 

 

access error

 

on the same network at the same time.

 

the same network at the same

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

time.

 

 

 

7FF8H

System error

 

The OS of the Q series C24 detected some error.

(

1)

 

 

 

7FFFH

 

 

 

 

 

 

 

 

 

 

 

 

 

B000H

 

 

 

 

Take corrective action by

 

 

 

 

 

 

 

 

referring to the CC-Link

 

 

 

to

Errors detected by the CC-Link module

 

 

 

 

 

Master/Local Module User's

 

 

 

BFFFH

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual.

 

 

 

 

 

 

 

 

 

 

 

 

C000H

 

 

 

 

Take corrective action by

 

 

 

to

Errors detected by the Ethernet module

 

referring to the Ethernet

 

 

 

CFFFH

 

 

 

 

 

Interface Module User's Manual.

 

 

 

F000H

 

 

 

 

Take corrective action by referring

 

 

 

 

 

Errors detected by the MELSECNET/H,

 

 

to MELSECNET/H,

 

 

 

to

 

 

 

 

 

 

MELSECNET/10 network system

 

MELSECNET/10 network system

 

 

 

FFFFH

 

 

 

 

 

 

 

 

 

 

 

 

reference manual.

 

 

 

 

 

 

 

 

 

 

 

 

10 - 22

10 - 22