6 F 3 B 0 3 6 2

7.1 T2N Special Relays and Registers

The Ethernet Port status information is reflected in the T2N special relays and special registers.

a.Special relays (the renewing cycle of 100 ms)

Special relay

Name

Function

 

 

 

 

S000B

Ethernet Port error

1:

The installed Ethernet Port unit is down.

 

(warning)

 

(The T2N continues to operate.)

 

 

0:

Reset the system from a user program after resolving the

 

 

 

error in the down Ethernet Port.

 

 

 

 

b.Special registers

T2N read out the internal station status of Ethernet Port and copy the SW register (the renewing cycle of 100 ms).

Special registers

Name

 

 

SW063

CH1 station status

 

 

c.Station status format

F E D C B A 9 8 7 6 5 4 3 2 1 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN

 

STBY

 

 

 

 

 

 

MTEN

 

 

 

 

TEST

 

 

 

INZ

 

 

RUN

 

 

 

 

 

 

 

 

STEN

 

 

 

 

Bit F: DOWN (down)

1: Down mode, 0: Other than down mode

Bit E: INZ (initialization)

1: Initialization in progress

 

0: Initialization completed

Bit D: STBY (standby)

1: Standby mode

 

0: Other than standby mode

Bit C: RUN (run)

1: Run mode, 0: Other than run mode

Bit 5: MTEN (Message transmission)

1: Enabled, 0: Prohibited

Bit 4: STEN (socket interface transmission)

1: Enabled, 0: Prohibited

Bit 0: TEST (test)

1: Test function execution in progress