6 F 3 B 0 3 6 2

b.Ethernet Port side (slave port)

START

Is the station status such that run + message transmission is enabled?

Yes

Does a response come back if a ping is issued to the main Ethernet Port?

Yes

Is the error counter read out from the RAS information constant (i.e., not being incremented)?

(Use RAS information readout to

determine this.)

Yes

END

No

Set the Ethernet Port to run + message

transmission enabled using an operating mode

 

 

control request.

 

 

 

 

 

 

No

1.

Check the main port side IP address.

2.

Verify that there is no router on the network.

 

 

3.

Check the network verification items.

 

 

 

 

No

It is possible that there is an abnormality on the

network itself. Check the network verification

 

 

items.

 

 

RAS error counters: Alignment error:

Short packet

CRC error

154

Page 155
Image 155