6 F 3 B 0 3 6 2
c.Status (See figure 4.3 for details on bits C, D, E and F.)
B B+1
F E D C B A 9 8 7 6 5 4 3 2 1 0
|
|
|
| 0 | 0 | 0 | 0 | TermSTS |
Detailed information (Only valid when TermSTS = 0BH.)
d.Important items
∙This request can be used in run and standby modes.
∙The read out RAS information is stored in the specified register area as shown below.
RAS information
word count
RAS information
←Specified register start address
←A register area whose size is the size of the read out RAS information plus one word must be allocated.
∙A boundary error (TermSTS = 0AH) occurs if it is not possible to allocate an area that is the size of the read out RAS information plus one word for the RAS information storage area.
∙A parameter error (TermSTS = 03H) occurs on any of the following transfer parameter settings.
∙If the RAS request type (Kind) is out of range (a value other than 1 to 5).
∙If the start position (Start) is out of range (a value of 4 or larger) for MIB information.
∙If the start position (Start) is out of range (a value of 161 or larger) for event trace information.
∙If the read count (ReadCnt) is out of range (a value of 31 or larger) for event trace information.