8.3 T2N Special Relays and Registers

The Ethernet Port status information is reflected in the T2N special relays and special registers.

1.Special relays

Special relay

Name

Function

 

 

 

 

S000B

Ethernet Port error

1:

The installed Ethernet Port unit is down.

 

(warning)

 

(The T2N continues to operate.)

 

 

0:

Reset the system from a user program after resolving the

 

 

 

error in the down Ethernet Port.

 

 

 

 

2.Special registers

Special registers

Name

 

 

SW063

CH1 station status

 

 

3.Station status format

F E D C B A 9 8 7 6 5 4 3 2 1 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN

 

STBY

 

 

 

 

 

 

MTEN

 

 

 

 

TEST

 

 

 

INZ

 

 

RUN

 

 

 

 

 

 

 

 

STEN

 

 

 

 

Bit F: DOWN (down)

1: Down mode, 0: Other than down mode

Bit E: INZ (initialization)

1: Initialization in progress

 

0: Initialization completed

Bit D: STBY (standby)

1: Standby mode

 

0: Other than standby mode

Bit C: RUN (run)

1: Run mode, 0: Other than run mode

Bit 5: MTEN (Message transmission)

1: Enabled, 0: Prohibited

Bit 4: STEN (socket interface transmission)

1: Enabled, 0: Prohibited

Bit 0: TEST (test)

1: Test function execution in progress

146