6 F 3 B 0 3 6 2

c.Receive request

START

 

 

 

 

No

Did the RECV instruction

complete?

 

 

Yes

 

Did the instruction time out?

No

TermSTS = 0BH

 

Details = 0020H

 

 

Yes

 

 

 

¬

 

 

 

Was the wait time set to

unlimited? Yes

¬

Is the station status such that run + socket transmission is enabled?

Yes

Is the local port open?

Yes

Resolve the problem by referring to the status.

 

Verify the status using the

No

procedure described in the item

3 " If a SEND or RECV

 

 

instruction fails complete" on

 

page 148.

 

 

No

Set the Ethernet Port to run +

socket transmission enabled

 

using an operating mode control

 

request.

 

 

 

 

No

Open UDP ports on the local

 

port.

 

 

Is the remote port

transmitting?

Yes

Are the remote port IP address and UDP port number correct?

Yes

Does a response come back

if a ping is issued to the

remote port?

Yes

Is the error counter read out from the RAS information constant (i.e., not being incremented)?

(Use RAS information

readout to determine this.)

Yes

END

No

Transmit a message at the

 

 

remote port.

 

 

 

 

 

 

No

Verify the remote port IP address and UDP port

 

number.

 

 

 

 

 

 

 

1.

Recheck the remote port IP address and

No

 

message transmission UDP port numbers.

 

2.

Verify that there is no router on the network.

 

3.

Check the network verification items.

 

 

 

 

No

It is possible that there is an abnormality on the

network itself. Check the network verification

 

 

items.

 

 

RAS error counters: Alignment error

Short packet

CRC error

157

Page 158
Image 158
Toshiba T2N instruction manual Receive request