6 F 3 B 0 3 6 2

*2 Includes the expansion F registers(Only T3H). One bank has 64K words (0 to 65535).

F 7 0

06

Bank number ... 00H: T3H internal registers

F0000 to F32767

01H: Expansion F registers (IC card) F0000 to F65535

02H: Expansion F registers (IC card) F0000 to F57343

*3 The T and C registers hold data that has flags attached.

Supplement:

The transfer data length has a maximum of 323 words when data is transferred over the Ethernet.

For the T registers, it is not possible to specify a range that spans both the basic T registers (0 to 511) and the expansion T registers (512 to 999). The T3H has the expansion

T register, but the T2N does not have.

c.Status (See figure 4.3 for details on bits C, D, E and F.)

B B+1

F E D C B A 9 8 7 6 5 4 3 2 1 0

 

 

 

 

0

0

0

0

TermSTS

Detailed information (Only valid when TermSTS = 0BH.)

d.Important items

The write operation is not synchronized with the remote port T2N/T3H scan operation.

If synchronization is necessary, applications must perform synchronization processing, such as transferring the data to a separate registers at the start of the T2N scan.

The command number (0021H) is the same as the "Data Read".

A transfer word count error (TermSTS = 09H) occurs if the transferred register data length exceeds the range 1 to 485 words (or 1 to 323 words for the T and C registers).

A register specification error (TermSTS = 01H) occurs if a value other than a stipulated value is specified for the register type codes (SRID/DRID).

A register specification error (TermSTS = 01H) occurs if 0007H (the T register) is specified for the local port register type code and a register other than the T register is specified for the remote port register type code. This also holds for the C register.

A boundary error (TermSTS = 0AH) occurs if a range spanning both the base T registers (0 to 511) and the expansion T registers (512 to 999) is specified for the T register.

For data storage registers, a boundary error occurs if the specified area (start register + register range) does not exist in either the local or remote ports.

Local port: TermSTS = 0AH, remote port: TermSTS = 8AH

A response timeout error (TermSTS = 02H) occurs if the response time from the remote port exceeds the time specified by the timer counter value.

59

Page 60
Image 60
Toshiba T2N instruction manual T and C registers hold data that has flags attached, Supplement