6 F 3 B 0 3 6 2
d.Important items
∙Values other than 1010H, 1020H, 1030H, and 2000H may not be specified for the specification information.
→Status: Transmission error (TermSTS = 0BH)
Detailed information: Incorrect control request specification (0083H)
∙Simultaneous run mode and standby mode requests (30x0H) cannot be executed.
→Status: Transmission error (TermSTS = 0BH)
Detailed information: Incorrect control request specification (0083H)
∙A mode that has already been established cannot be requested. However, requests that change the MTEN/STEN state within the same mode do not cause an error.
→Status: Transmission error (TermSTS = 0BH)
Detailed information: Incorrect control request specification (0083H)
∙No execution is possible in down mode.
→Status: Module error/initialization in progress (TermSTS = 06H)
∙An error occurs if a control request that switches the Ethernet Port to run mode is issued without first setting the IP address.
→Status: Transmission error (TermSTS = 0BH)
Detailed information: MAC/IP not set up (0050H)
e.Sample program
This sample ladder program issues a operating mode control request to the channel 1 Ethernet Port.
This program is executed by turning on the R0503 A point.
Parameters: 12544:3100H, 00019:0013H
04144:1030H
R0503 |
|
| R0603 | |
| ( | |||
| /* Control request | */ |
| |
R0603 |
|
|
| |
RW000][ 00019 MOV RW001] | ||||
/* Designates the module and sets the CMD number. */ | ||||
|
| |||
+[ 04144 MOV | ||||
/* Setup specified information. */ |
| |||
|
| |||
+[RW000 SEND | RW010][ RST | |||
| /* Sets the request. | */ |
| |
|
|
| ||
|
|
|
|
|