7.2 Down Information
When an Ethernet Port goes to down mode, the factor that caused that transition is stored in the T2N interface buffer as one word of data. This data can be read by the T2N with the READ instruction.
Table 7.1 lists the down information error codes and the factors that caused the transition to down mode.
Table 7.1 Down Information
Error code (H) | Interpretation |
0010 | Watchdog timeout |
|
|
0020 | Memory bus stall |
0030 | A TRAP occurred |
|
|
0040 | Jabbering timeout |
0050 | LAN controller check error |
|
|
0160 | ROM BCC check data match error |
|
|
0260 | System RAM area check error |
0360 | T2N interface buffer check error |
|
|
0500, 0501 | Semaphore acquisition error |
0502, 0503 | Semaphore acquisition error |
|
|
0504 | MBX receive error |
|
|
0505 | MBX send error |
0506 | TCP resend queue full |
|
|
0507 | Acquired buffer in use |
0508 | Error in acquiring initial buffer |
|
|
Important items
This is a
Sample: Down information readout
R0000 |
READ instruction description
H00FE: Module designation ... Ethernet Port must specify H00FE.
RW010: Specifies the 04081 (0FF1H) down information area. 0FF1H is the down information area for the Ethernet Port.
RW011: Specifies the number of words (00001) to be read out.
D1000: Specifies the register in which to store the read out down information.
In this case, the down information that is read out is stored in D1000.
The down information is stored in D1000 by turning R0000 on.