E6581160

2.2Description of terminals

2.2.1Power circuit terminals

In case of the lug connector, cover the lug connector with insulated tube, or use the insulated lug connector.

 

 

 

Screw size

 

tightening torque

 

 

 

2

 

 

 

 

 

M3.5 screw

 

0.9Nm

 

7.1lb y in

 

 

 

 

M4 screw

 

1.3Nm

 

10.7lb y in

 

 

 

 

M5 screw

 

2.5Nm

 

22.3lb y in

 

 

 

 

M6 screw

 

4.5Nm

 

40.1lb y in

 

 

Q Power circuit

 

 

 

 

 

 

 

Terminal symbol

 

 

Terminal function

 

 

 

 

 

 

 

Grounding terminal for connecting inverter. There are 3 terminals in total. 2 terminals in

 

 

 

 

 

 

 

the terminal board, 1 terminal in the cooling fin.

 

 

 

 

 

 

 

240V class: single-phase 200 to 240V-50/60Hz

 

 

 

 

 

 

 

 

three-phase 200 to 240V-50/60Hz

 

 

R/L1,S/L2,T/L3

500V class: three-phase 380 to 500V-50/60Hz

 

 

 

 

 

 

 

600V class: three-phase 525 to 600V-50/60Hz

 

 

 

 

 

 

 

* Single-phase input: R/L1 and S/L2 terminals

 

 

U/T1,V/T2,W/T3

Connect to a (three-phase induction) motor.

 

 

PA/+PB

Connect to braking resistors.

 

 

 

 

 

Change parameters H, H, H, H if necessary.

 

 

 

 

 

 

 

 

 

PC/-

This is a negative potential terminal in the internal DC main circuit. DC common power

 

 

can be input across the PA terminals (positive potential).

 

 

 

 

 

 

 

 

 

POPA/+

Terminals for connecting a DC reactor (DCL: optional external device). Shorted by a

 

 

short bar when shipped from the factory. Before installing DCL, remove the short bar.

 

 

 

 

 

 

 

2.2.2Selection of wiring materials

 

Capacity of

 

 

 

Wire size (See Note 4)

 

Voltage class

applicable

Inverter model

Power circuit

DC reactor

Braking resistor/

Earth cable

(mm2) (Note 1.)

(optional) (mm2)

Braking unit

(mm2)

 

motor (kW)

 

 

 

 

(optional) (mm2)

 

 

0.2

VFS11S-2002PL

2.0

(2.0)

2.0

2.0

3.5

Single-phase

0.4

VFS11S-2004PL

2.0

(2.0)

2.0

2.0

3.5

0.75

VFS11S-2007PL

2.0

(2.0)

2.0

2.0

3.5

240V class

1.5

VFS11S-2015PL

2.0

(2.0)

2.0

2.0

3.5

 

 

2.2

VFS11S-2022PL

2.0

(2.0)

3.5

2.0

3.5

 

0.4

VFS11-2004PM

2.0

(2.0)

1.25

2.0

3.5

 

0.55

VFS11-2005PM

2.0

(2.0)

2.0

2.0

3.5

 

0.75

VFS11-2007PM

2.0

(2.0)

2.0

2.0

3.5

Three-phase

1.5

VFS11-2015PM

2.0

(2.0)

2.0

2.0

3.5

2.2

VFS11-2022PM

2.0

(2.0)

2.0

2.0

3.5

240V class

4.0

VFS11-2037PM

2.0

(2.0)

3.5

2.0

3.5

 

5.5

VFS11-2055PM

5.5

(2.0)

8.0

2.0

5.5

 

7.5

VFS11-2075PM

8.0

(5.5)

14

3.5

5.5

 

11

VFS11-2110PM

14 (8.0)

14

5.5

8.0

 

15

VFS11-2150PM

22

(14)

22

14

8.0

12

Page 13
Image 13
Toshiba VF-S11 manual Description of terminals, Power circuit terminals, Selection of wiring materials