Toshiba VF-S11 manual QTable of output terminal functions, E6581160

Models: VF-S11

1 81
Download 81 pages 58.25 Kb
Page 69
Image 69
QTable of output terminal functions 2

E6581160

QTable of output terminal functions 2

 

 

Function

Code

Function

Action

 

 

No.

 

 

 

 

 

 

 

12

OT

Over-torque detection

ON: Torque current is equal to or larger than

 

 

 

 

 

H set value and longer than H

 

 

 

 

 

set time.

 

 

 

 

 

OFF: The torque current is equal to or less than

 

 

 

 

 

(H set value - H set value).

 

 

13

OTN

Inversion of over-torque detection

Inversion of OT

 

 

14

RUN

Start/Stop

ON: When operation frequency is output or during

 

 

 

 

 

(FD)

 

 

 

 

 

OFF: Operation stopped

 

 

15

RUNN

Inversion of RUN/STOP

Inversion of RUN setting

 

 

16

POL

OL pre-alarm

ON: 50% or more of calculated value of overload

 

 

 

 

 

protection level

 

 

 

 

 

OFF: Less than 50% of calculated value of

 

 

 

 

 

overload protection level

 

 

17

POLN

Inversion of OL pre-alarm

Inversion of POL setting

 

 

18

POHR

Braking resistor overload pre-alarm

ON: 50% or more of calculated value of H

 

 

 

 

 

set overload protection level

 

 

 

 

 

OFF: Less than 50% of calculated value of

 

 

 

 

 

H set overload protection level

 

 

19

POHRN

Inversion of braking resistor overload pre-alarm

Inversion of RCHR setting

 

 

20

POT

Over-torque detection pre-alarm

ON: Torque current is equal to or larger than 70%

 

 

 

 

 

of H set value.

 

 

 

 

 

OFF: The torque current is below (H set

 

 

 

 

 

value x 70% - H set value).

 

 

21

POTN

Inversion of over-torque detection pre-alarm

Inversion of POT setting

7

 

22

PAL

Pre-alarm

One of the following is turned on:

 

 

 

 

ON POL, POHR, POT, MOFF, UC, OT, LL

 

 

 

 

stop, COT, and momentary power failure

 

 

 

 

 

slowdown stop.

 

 

 

 

 

or E,R,QTJ issues an alarm

 

 

 

 

 

All the following are turned off:

 

 

 

 

 

OFF POL, POHR, POT, MOFF, UC, OT, LL

 

 

 

 

 

stop, COT, and momentary power failure

 

 

 

 

 

slowdown stop.

 

 

 

 

 

or E,R,QTJ issues no alarm

 

 

23

PALN

Inversion of pre-alarm

Inversion of PAL setting

 

 

24

UC

Small-current detection

ON: The output current is equal to or less than

 

 

 

 

 

H set value for H set time.

 

 

 

 

 

OFF: The output current is equal to or larger than

 

 

 

 

 

H set value + 10%.

 

 

25

UCN

Inversion of small-current detection

Inversion of UC setting

 

 

26

HFL

Significant failure

ON: QEC,QEN,QV,G,

 

 

 

 

 

GGR,GVP,GRJQ,GTT-

 

 

 

 

 

,QJ,WR,GH,WE,

 

 

 

 

 

GV[R,QTGRJ)

 

 

 

 

 

OFF: Failure other than the above

 

 

27

HFLN

Inversion of significant failure

Inversion of HFL setting

 

 

28

LFL

Insignificant failure

ON: (QE-,QR-,QJ,

 

 

 

 

 

QN-,QNT)

 

 

 

 

 

OFF: Failure other than the above

 

 

29

LFLN

Inversion of insignificant failure

Inversion of LFL setting

 

 

30

RDY1

Ready for operation (including ST/RUN)

ON: Ready for operation (ST and RUN are also

 

 

 

 

 

ON)

 

 

 

 

 

OFF: Others

 

 

31

RDY1N

Inversion of ready for operation (including

Inversion of RDY1 setting

 

 

 

 

ST/RUN)

 

 

 

32

RDY2

Ready for operation (excluding ST/RUN)

ON: Ready for operation (ST and RUN are not

 

 

 

 

 

ON)

 

 

 

 

 

OFF: Others

 

 

33

RDY2N

Inversion of ready for operation (excluding ST/RUN)

Inversion of RDY2

 

 

34

FCVIB

Frequency VIB selection

ON: VIB selected as frequency command

 

 

 

 

 

OFF: Terminal other than VIB selected as

 

 

 

 

 

frequency command

68

Page 69
Image 69
Toshiba VF-S11 manual QTable of output terminal functions, E6581160