3. Operations

E6581160

3. Operations

3.1Simplified Operation of the VF-S11

The procedures for setting operation frequency and the methods of operation can be selected from the following.

Start / Stop

:

(1)

Start and stop using the operation panel keys

 

 

(2)

Run and stop from the operation panel

 

 

3

 

 

 

:

(1)

Setting using the potentiometer on the inverter

Setting the frequency

 

 

 

main unit

 

(2)Setting using the operation panel

(3)Setting using external signals to the terminal board (0-10Vdc, 4-20mAdc)

Use the basic parameters EOQF (Operation command mode selection), HOQF (Speed setting mode selection).

Title

Function

Adjustment range

Default setting

EOQF

Command mode selection

0: Terminal board

1

1: Panel

 

 

 

 

 

0: Internal potentiometer setting

 

 

 

1: VIA

 

 

 

2: VIB

 

HOQF

Frequency setting mode

3: Operation panel

0

 

 

4: Serial communication

 

 

 

5: External contact up/down

 

 

 

6: VIA+VIB (Override)

 

*See the manual E6581158 for HOQF=4, 5 and 6.