3

E6581160

Operation frequency setting, running and stopping using external Ex.4 signals.

(1)

Wiring

 

 

 

 

 

 

 

 

 

 

PO

PA/+

PB

PC/-

 

 

 

MCCB

R/L1

 

 

 

 

U/T1

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S/L2

*

Power circuit

 

V/T2

IM

 

 

T/L3

Noise

 

W/T3

 

 

filter

 

 

 

 

 

 

 

 

Braking

 

 

F

Run forward signal

 

 

 

 

 

 

 

 

 

 

 

circuit

 

 

R

Run backward signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIA

Current signal: 420mA

 

 

 

 

 

 

 

 

 

 

 

 

CC

VIA

VIB

PP

 

 

 

 

 

 

 

 

 

Voltage signal: 010V

 

 

 

 

 

 

 

External potentiometer

 

 

 

 

 

(Otherwise, input voltage signal (0~10V) between the terminals VIA-CC.)

(2)

Parameter setting

 

 

 

Title

 

Function

Programmed value

 

EOQF

 

Command mode selection

0

 

HOQF

 

Frequency setting mode selection

1or2

(3)

Operation

 

 

Run/stop: ON/OFF input to F-CC, R-CC. (Set SW1 to Sink logic)

Frequency setting: VIA and VIB: 0-10Vdc (External potentiometer)

VIA: Input 4-20mAdc.

Note) Use the VIA slide switch to switch between voltage and current to the VIA terminal.

Voltage input: V side

Current input: I side

* 600V models have no noise filter inside.

26

Page 27
Image 27
Toshiba VF-S11 manual Via