Toshiba VF-S11 manual 7.3Extended parameters, Input/output parameters, E6581160

Models: VF-S11

1 81
Download 81 pages 58.25 Kb
Page 54
Image 54
7.3Extended parameters

E6581160

7.3Extended parameters

Input/output parameters 1

 

 

 

 

Minimum

 

 

 

 

 

 

Title

Communication

Function

Unit

setting unit

Adjustment range

Default

User

Reference

 

No.

Panel/Commun

setting

setting

E6581158

 

 

 

 

 

 

 

 

 

 

 

ication

 

 

 

 

 

 

H

0100

Low-speed signal

Hz

0.1/0.01

0.0-HJ

0.0

 

6.1.1

 

 

 

 

output frequency

 

 

 

 

 

 

 

 

H

0101

Speed reach

Hz

0.1/0.01

0.0-HJ

0.0

 

6.1.3

 

 

 

 

setting frequency

 

 

 

 

 

 

 

 

H

0102

Speed reach

Hz

0.1/0.01

0.0-HJ

2.5

 

6.1.2

 

 

 

 

detection band

 

 

 

 

 

 

 

 

H

0105

Priority selection

-

-

0: Reverse

1

 

6.2.1

 

 

 

 

(Both F-CC and

 

 

1: Slowdown Stop

 

 

 

 

 

 

 

R-CC are ON)

 

 

 

 

 

 

 

 

H

0108

Always active

-

-

0-65 (No function)

0

 

6.3.1

 

 

 

 

function selection 1

 

 

 

 

 

 

 

 

H

0109

Analog/contact

-

-

0: Analog input for communications

0

 

6.2.2

 

 

 

 

input function

VIB - analog input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selection (VIA/VIB

 

 

1: VIA - analog input

 

 

 

 

 

 

 

terminal)

 

 

VIB - contact input (Sink)

 

 

 

 

 

 

 

 

 

 

2: VIA - analog input

 

 

 

 

 

 

 

 

 

 

VIB - contact input (Source)

 

 

 

 

 

 

 

 

 

 

3: VIA - contact input (Sink)

 

 

 

 

 

 

 

 

 

 

VIB - contact input (Sink)

 

 

 

 

7

 

 

 

 

 

4: VIA - contact input (Source)

 

 

 

 

 

 

 

 

 

VIB - contact input (Source)

 

 

 

 

H

0110

Always-active

-

-

0-65 (ST)

1

 

6.3.1

 

 

 

 

function selection 2

 

 

 

 

 

 

 

 

H

0111

Input terminal

-

-

0-65 (F)

2

 

6.3.2

 

 

 

 

selection 1 (F)

 

 

 

 

 

 

 

 

H

0112

Input terminal

-

-

0-65 (R)

3

 

 

 

 

 

 

selection 2 (R)

 

 

 

 

 

 

 

 

H

0113

Input terminal

-

-

0-65 (RES)

10

 

 

 

 

 

 

selection 3 (RES)

 

 

 

 

 

 

 

 

H

0114

Input terminal

-

-

0-65 (SS1)

6

 

 

 

 

 

 

selection 4 (S1)

 

 

 

 

 

 

 

 

H

0115

Input terminal

-

-

0-65 (SS2)

7

 

 

 

 

 

 

selection 5 (S2)

 

 

 

 

 

 

 

 

H

0116

Input terminal

-

-

0-65 (SS3)

8

 

 

 

 

 

 

selection 6 (S3)

 

 

 

 

 

 

 

 

H

0117

Input terminal

-

-

5-17 (SS4)

9

 

 

 

 

 

 

selection 7 (VIB)

 

 

 

 

 

 

 

 

H

0118

Input terminal

-

-

5-17 (AD2)

5

 

 

 

 

selection 8 (VIA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output terminal

 

 

0-255 (LOW)

4

 

6.3.3

 

 

H

0130

selection 1A

-

-

 

 

 

 

 

 

 

 

(RY-RC)

 

 

 

 

 

 

 

 

H

0131

Output terminal

-

-

0-255 (RCH)

6

 

 

 

 

 

 

selection 2A

 

 

 

 

 

 

 

 

 

 

(OUT-NO)

 

 

 

 

 

 

 

 

H

0132

Output terminal

-

-

0-255 (FL)

10

 

 

 

 

 

 

selection 3 (FL)

 

 

 

 

 

 

 

 

H

0137

Output terminal

-

-

0-255 (always ON)

255

 

6.3.4

 

 

 

 

selection 1B

 

 

 

 

 

 

 

 

 

 

(RY-RC)

 

 

 

 

 

 

 

 

H

0138

Output terminal

-

-

0-255 (always ON)

255

 

 

 

 

 

 

selection 2B

 

 

 

 

 

 

 

 

 

 

(OUT-NO)

 

 

 

 

 

 

 

 