Ex.3

E6581160

Ex.3

Setting the operation frequency using built-in potentiometer and

running and stopping using external signals.

 

 

(1)

Wiring

 

 

 

 

 

 

 

 

 

 

 

PO

PA/+

PB

PC/-

 

 

 

 

MCCB

R/L1

 

 

 

 

U/T1

Motor

 

 

 

 

 

 

 

3

 

 

*

 

 

 

 

 

 

S/L2

 

 

 

V/T2

 

 

 

Noise

Power circuit

IM

 

 

T/L3

filter

W/T3

 

 

 

 

 

 

 

 

 

 

 

Braking

 

 

F

Run forward

 

 

 

 

 

circuit

 

 

R

signal

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

backward

 

 

 

 

 

 

 

 

 

signal

 

 

 

 

 

 

 

 

CC

Common

 

 

 

 

 

 

 

 

 

 

(2)

Parameter setting

 

 

 

Title

 

Function

Programmed value

 

EOQF

 

Command mode selection

0

 

HOQF

 

Frequency setting mode selection

0

(3)

Operation

 

 

Run/stop: ON/OFF input to F-CC, R-CC. (Set SW1 to Sink logic)

Frequency setting: Set adjusting position of notches on the potentiometer.

* 600V models have no noise filter inside.