E6581160
QTable of input terminal functions 3
Function | Code | Function | Action | |
No. | ||||
|
|
| ||
54 | STN | Coast stop (gate off) | ON: Coast stop (gate off) | |
55 | RESN | Inversion of RES | ON: Acceptance of reset command | |
|
|
| OFF→ ON: Trip reset | |
56 | F+ST | Combination of forward run and standby | ON: Simultaneous input from F and ST | |
57 | R+ST | Combination of reverse run and standby | ON: Simultaneous input from R and ST | |
58 | AD3 | Acceleration/deceleration 3 selection | ON: Acceleration/deceleration 3 | |
|
|
| OFF: Acceleration/deceleration 1 or 2 | |
59 | F+AD3 | Combination of forward run and | ON: Simultaneous input from F and AD3 | |
|
| acceleration/deceleration 3 |
| |
60 | R+AD3 | Combination of reverse run and | ON: Simultaneous input from R and AD3 | |
|
| acceleration/deceleration 3 |
| |
61 | OCS2 | Forced switching of stall prevention level 2 | ON: Enabled at the value of H | |
|
|
| OFF: Enabled at the value of H | |
62 | HDRY | Holding of | ON: Once turned on, | |
|
|
| OFF: The status of | |
|
|
| according to conditions. | |
63 | HDOUT | Holding of | ON: Once turned on, | |
|
|
| OFF: The status of | |
|
|
| according to conditions. | |
64 | PRUN | Cancellation (clearing) of operation command from | 0: Operation command canceled (cleared) | |
|
| panel | 1: Operation command retained | |
65 | ICLR | PID control integral value clear | ON: PID control integral value always zero | |
|
|
| OFF: PID control permitted |
Q Table of output terminal functions 1 |
|
| 7 | ||
Function | Code | Function | Action |
| |
No. |
|
|
|
|
|
0 | LL | Frequency lower limit | ON: The output frequency is above the NN set |
|
|
|
|
| value. |
|
|
|
|
| OFF: The output frequency is equal to or less than |
|
|
|
|
| the NN set value. |
|
|
1 | LLN | Inversion of frequency lower limit | Inversion of LL setting |
|
|
2 | UL | Frequency upper limit | ON: Output frequency is equal to or higher than |
|
|
|
|
| WN value. |
|
|
|
|
| OFF: Output frequency is lower than WN value. |
|
|
3 | ULN | Inversion of frequency upper limit | Inversion of UL setting |
|
|
4 | LOW | ON: Output frequency is equal to or higher than |
|
| |
|
|
| H value. |
|
|
|
|
| OFF: Output frequency is lower than H |
|
|
|
|
| value. |
|
|
5 | LOWN | Inversion of | Inversion of LOW setting |
|
|
6 | RCH | Designated frequency attainment signal | ON: The output frequency is equal to or less than |
|
|
|
| (completion of acceleration/deceleration) | the specified frequency ± frequency set with |
|
|
|
|
| H. |
|
|
|
|
| OFF: The output frequency is above the specified |
|
|
|
|
| frequency ± frequency set with H. |
|
|
7 | RCHN | Inversion of designated frequency attainment | Inversion of RCH setting |
|
|
|
| signal (inversion of completion of |
|
|
|
|
| acceleration/deceleration) |
|
|
|
8 | RCHF | Set frequency attainment signal | ON: The output frequency is equal to or less than |
|
|
|
|
| the frequency set with H ± H. |
|
|
|
|
| OFF: The output frequency is above the frequency |
|
|
|
|
| set with H ± H. |
|
|
9 | RCHFN | Inversion of set frequency attainment signal | Inversion of RCHF setting |
|
|
10 | FL | Failure signal (trip output) | ON: When inverter is tripped |
|
|
|
|
| OFF: When inverter is not tripped |
|
|
11 | FLN | Inversion of failure signal (inversion of trip output) | Inversion of FL setting |
|
|
67