E6581160
(3)Setting the frequency using the operation panel (HOQF= or )
Frequency setting
1)Setting the frequency using external potentiometer
3
PP
VIB
CC
| ★Potentiometer |
| |
| Setting frequency using the potentiometer | ||
: Setting frequency | 60Hz |
|
|
using potentiometer |
|
| |
| Frequency |
|
|
| 0 |
| MAX |
|
| ||
| MIN |
*The input terminal VIA can be used in the same way. HOQF=: VIA effective, HOQF=: VIB effective
2)Setting the frequency using input voltage (0~10V)
+
-
VIA
CC
★Voltage signal
Setting frequency using voltage signals (0∼10V).
: Voltage signal
60Hz
Frequency
0
0Vdc10Vdc
*The input terminal VIB can be used in the same way. HOQF=: VIA effective, HOQF=: VIB effective
Note: Be sure to turn the VIA slide switch to the V (voltage) position.
3)Setting the frequency using current input (4~20mA)
+
-
VIA
CC
★Current Signal
Current signal Setting frequency using current signals (4~20mA).
: Current signal
60Hz
Frequency
0 | 4mAdc | 20mAdc |
|
* Setting of parameters also allow
Note: Be sure to turn the VIA slide switch to the I (current) position.
22