Toshiba VF-S11 manual E6581160

Models: VF-S11

1 81
Download 81 pages 58.25 Kb
Page 67
Image 67
Manual background

E6581160

QTable of input terminal functions 2

 

 

Function

Code

Function

Action

 

 

No.

 

 

 

 

 

 

 

34

F+SS3+AD2

Combination of forward run, preset-speed

ON: Simultaneous input from F, SS3 and AD2

 

 

 

 

command 3 and acceleration/deceleration 2

 

 

 

35

R+SS3+AD2

Combination of reverse run, preset-speed

ON: Simultaneous input from R, SS3 and AD2

 

 

 

 

command 3 and acceleration/deceleration 2

 

 

 

36

F+SS4+AD2

Combination of forward run, preset-speed

ON: Simultaneous input from F, SS4 and AD2

 

 

 

 

command 4 and acceleration/deceleration 2

 

 

 

37

R+SS4+AD2

Combination of reverse run, preset-speed

ON: Simultaneous input from R, SS4 and AD2

 

 

 

 

command 4 and acceleration/deceleration 2

 

 

 

38

FCHG

Frequency command forced switching

ON: H(If H = )

 

 

 

 

 

OFF: HOQF

 

 

39

VF2

No.2 Switching of V/F setting

ON: No.2 V/F setting

 

 

 

 

 

(RV=0, H, H, H, H)

 

 

 

 

 

OFF: No.1 V/F setting

 

 

 

 

 

(Set value of RV, XN, XNX, XD, VJT)

 

 

40

MOT2

No.2 motor switching

ON: No.2 motor

 

 

 

 

VF2AD2OCS2

(RV=0, H, H, H, H,

 

 

 

 

 

H, H, H, H)

 

 

 

 

 

OFF: No.1 motor (Set value of RV, XN, XNX,

 

 

 

 

 

XD, VJT, CEE, FGE, H, H)

 

 

41

UP

Frequency UP signal input from external contacts

ON: Increase in frequency

 

 

42

DOWN

Frequency DOWN signal input from external

ON: Reduction in frequency

 

 

 

 

contacts

 

 

 

43

CLR

Frequency UP/DOWN cancellation signal input

OFFON: Resetting of UP/DOWN frequency by

 

 

 

 

from external contacts

means of external contacts

 

 

44

CLR+RES

Combination of frequency UP/DOWN cancellation

ON: Simultaneous input from CLR and RES

7

 

 

 

and reset by means of external contacts

 

 

45

EXTN

Inversion of trip stop command from external

OFF: G Trip stop

 

 

 

device

 

 

 

46

OH

Thermal trip stop signal input from external device

ON: QJ Trip stop

 

 

47

OHN

Inversion of thermal trip stop command from

OFF: QJ Trip stop

 

 

 

 

external device

 

 

 

48

SC/LC

Forced switching from remote to local control

Enabled when remote control is exercised

 

 

 

 

 

ON: Local control (setting of cmod, HOQF and

 

 

 

 

 

H)

 

 

 

 

 

OFF: Remote control

 

 

49

HD

Operation holding (stop of 3-wire operation)

ON: F (forward run)/R: (reverse run) held, 3-wire

 

 

 

 

 

operation

 

 

 

 

 

OFF: Slowdown stop

 

 

50

CMTP

Forced switching of command mode and terminal

ON: Terminal board operation

 

 

 

 

board command

OFF: Setting of EOQF

 

 

51

CKWH

Display cancellation of the cumulative power

ON: Monitor display cancellation of the cumulative

 

 

 

 

amount (kWh)

power amount (kWh)

 

 

52

FORCE

Forced operation (factory configuration required)

ON: Forced operation mode in which operation is

 

 

 

 

 

not stopped in the event of the occurrence of

 

 

 

 

 

a soft fault (preset speed operation frequency

 

 

 

 

 

15) To use this function, the inverter needs to

 

 

 

 

 

be so configured at the factory.

 

 

 

 

 

OFF: Normal operation

 

 

53

FIRE

Fire-speed control

ON: Fire-speed operation (preset speed operation

 

 

 

 

 

frequency 15)

 

 

 

 

 

OFF: Normal operation

Note. When function 1, 10-12, 15-17, 38, 41-45 or 48 is assigned to an input terminal board, the input terminal board is enabled even if the parameter command mode selection cmod is set at 1 (panel).

66

Page 67
Image 67
Toshiba VF-S11 manual E6581160