E6581160

9.Before making a service call

- Trip information and remedies

9.1Trip causes/warnings and remedies

When a problem arises, diagnose it in accordance with the following table.

If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table, contact your Toshiba dealer.

[Trip information]

 

 

Error code

Failure code

Problem

Possible causes

Remedies

 

 

QE

0001

Overcurrent during

The acceleration time CEE is too short.

Increase the acceleration time CEE.

 

 

QER

0025

acceleration

The V/F setting is improper.

Check the V/F parameter.

 

 

 

 

Overcurrent flowing

A restart signal is imput to the rotating

Use H (auto-restart) and H

 

 

 

 

in element during

motor after a momentary stop, etc.

(ride-through control).

 

 

 

 

acceleration

A special motor (e.g. motor with a small

Adjust the carrier frequency H.

 

 

 

 

 

impedance) is used.

Set the carrier frequency control mode

 

 

 

 

 

 

selection parameter f316 to 1 or 3

 

 

 

 

 

 

(carrier frequency decreased

 

 

 

 

 

 

automatically).

 

 

QE

0002

Overcurrent during

The deceleration time FGE is too short.

Increase the deceleration time FGE.

 

 

QER

0026

deceleration

 

Set the carrier frequency control mode

 

 

 

 

Overcurrent flowing

 

selection parameter f316 to 1 or 3

 

 

 

 

in element during

 

(carrier frequency decreased

 

 

 

 

decelearion

 

automatically).

 

 

QE

0003

Overcurrent during

The load fluctuates abruptly.

Reduce the load fluctuation.

9

 

QER

0027

constant speed

The load is in an abnormal condition.

Check the load (operated machine).

 

 

 

operation

 

Set the carrier frequency control mode

 

 

 

Overcurrent flowing

 

selection parameter f316 to 1 or 3

 

 

 

 

in element during

 

(carrier frequency decreased

 

 

 

 

operation

 

automatically).

 

 

ER

0025

Ground fault trip

A current leaked from an output cable or

Check cables, connectors, and so on for

 

 

ER

0026

Arm overcurrent at

the motor to ground.

ground faults.

 

 

0027

start-up

A main circuit elements is defective.

Make a service call.

 

 

ER

 

(for 11 and 15 kW

 

 

 

 

 

 

models only)

 

 

 

 

QEN

0004

Overcurrent (An

The insulation of the output main circuit or

Check the cables and wires for defective

 

 

 

 

overcurrent on the

motor is defective.

insulation.

 

 

 

 

load side at start-up)

The motor has too small impedance.

When using a 11 or 15 kW model, check

 

 

 

 

 

A 11 or 15 kW model was started,

cables, connectors, and so on for ground

 

 

 

 

 

although a current is leaked from an

faults.

 

 

 

 

 

output cable or the motor to ground.

 

 

 

QEC

0005

Arm overcurrent at

A main circuit elements is defective.

Make a service call.

 

 

 

 

start-up

 

 

 

 

*

0008

Input phase failure

A phase failure occured in the input line of

Check the main circuit input line for phase

 

 

GRJ

 

 

the main circuit.

failure.

 

 

 

 

The capacitor in the main circuit lacks

Enable H (input phase failure

 

 

 

 

 

 

 

 

 

 

capacitance.

detection).

 

 

 

 

 

 

Check the capacitor in the main circuit for

 

 

 

 

 

 

exhaustion.

 

 

*

0009

Output phase failure

A phase failure occurred in the output line

Check the main circuit output line, motor,

 

 

GRJQ

 

 

of the main circuit.

etc. for phase failure.

 

 

 

 

 

Enable H (Output phase failure

 

 

 

 

 

 

 

 

 

 

 

 

detection).

*You can select a trip ON/OFF by parameters. (Continued overleaf)

76

Page 77
Image 77
Toshiba VF-S11 manual Before making a service call Trip information and remedies, Trip causes/warnings and remedies