E6581160
QAIC, Fuse and Wire sizes
Voltage | Capacity of |
| AIC (A) | Fuse class and current | Wire sizes of |
|
|
applicable motor | Inverter model |
|
| ||||
class | (Interrupting capacity) | (A) | power circuit |
|
| ||
(kW) |
|
|
| ||||
|
|
|
|
|
|
| |
| 0.2 | AIC 1000A | CC/J 6A max. | AWG 14 |
|
| |
0.4 | AIC 1000A | CC/J 10A max. | AWG 14 |
|
| ||
0.75 | AIC 1000A | CC/J 15A max. | AWG 14 |
|
| ||
240V class |
|
| |||||
1.5 | AIC 1000A | CC/J 20A max. | AWG 12 |
|
| ||
|
|
| |||||
| 2.2 | AIC 1000A | CC/J 30A max. | AWG 10 |
|
| |
| 0.4 | AIC 5000A | CC/J 6A max. | AWG 14 |
|
| |
| 0.55 | AIC 5000A | CC/J 10A max. | AWG 14 |
|
| |
| 0.75 | AIC 5000A | CC/J 10A max. | AWG 14 |
|
| |
| 1.5 | AIC 5000A | CC/J 15A max. | AWG 14 |
|
| |
2.2 | AIC 5000A | CC/J 20A max. | AWG 12 |
|
| ||
240V class | 4.0 | AIC 5000A | J 35A max. | AWG 10 |
|
| |
|
|
|
|
|
|
|
|
| 5.5 | AIC 22000A | J 50A max. | AWG 8 |
| 6 | |
| 7.5 | AIC 22000A | J 60A max. | AWG 6 |
| ||
| 11 | AIC 22000A | J 80A max. | AWG 4 |
|
| |
| 15 | AIC 22000A | J 110A max. | AWG 6x2 |
|
| |
| 0.4 | AIC 5000A | CC/J 3A max. | AWG 14 |
|
| |
| 0.75 | AIC 5000A | CC/J 6A max. | AWG 14 |
|
| |
| 1.5 | AIC 5000A | CC/J 10A max. | AWG 14 |
|
| |
2.2 | AIC 5000A | CC/J 15A max. | AWG 14 |
|
| ||
4.0 | AIC 5000A | CC/J 20A max. | AWG 12 |
|
| ||
500V class |
|
| |||||
5.5 | AIC 22000A | CC/J 30A max. | AWG 10 |
|
| ||
|
|
| |||||
| 7.5 | AIC 22000A | J 35A max. | AWG 8 |
|
| |
| 11 | AIC 22000A | J 50A max. | AWG 8 |
|
| |
| 15 | AIC 22000A | J 70A max. | AWG 6 |
|
| |
| 0.75 | AIC 5000A | CC/J 6A max. | AWG 14 |
|
| |
| 1.5 | AIC 5000A | CC/J 6A max. | AWG 14 |
|
| |
| 2.2 | AIC 5000A | CC/J 10A max. | AWG 14 |
|
| |
4.0 | AIC 5000A | CC/J 15A max. | AWG 14 |
|
| ||
600V class | 5.5 | AIC 22000A | CC/J 20A max. | AWG 10 |
|
| |
| 7.5 | AIC 22000A | CC/J 25A max. | AWG 10 |
|
| |
| 11 | AIC 22000A | J 30A max. | AWG 8 |
|
| |
| 15 | AIC 22000A | J 45A max. | AWG 8 |
|
|
6.2.4Motor thermal protection
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor. In case of multi motor operation with one inverter, thermal relay should be connected to each motor.
49