| TROUBLESHOOTING |
|
| |
TABLE 50 – TROUBLESHOOTING |
|
|
|
|
|
|
|
|
|
PROBLEM |
| CAUSE |
| SOLUTION |
|
|
| ||
No display on panel. | 1. No 115VAC to 1T. | 1a. Check wiring and fuse | ||
Unit will not operate. |
|
|
| 3FU |
|
|
| b. Check wiring emergency | |
|
|
|
| stop contacts 5 to L of CTB2 |
|
|
|
| Terminal Block. |
|
|
| c. Replace 1T | |
| 2. | No 24VAC to Microboard | 2. | Check wiring 1T to |
|
|
|
| Microboard. |
| 3. | 1T defective, no | 3. Replace 1T | |
|
| 24VAC output. |
|
|
| 4. | Short in wire to temp. sensors | 4. | Unplug connections at |
|
| or pressure transducers. |
| Microboard to isolate. |
| 5. | Defective Microboard | 5. | Replace Microboard. |
|
| or Display board. |
|
|
|
|
| NOTE: Contact YORK | |
|
|
|
| Service before |
|
|
|
| Replacing circuit Boards! |
|
|
|
| |
“FLOW SWITCH/REM | 1. No chilled liquid flow. | 1. | Check chilled liquid flow. | |
STOP NO RUN PERMISSIVE” |
|
|
|
|
| 2. | Flow switch improperly | 2. | Check that the flow switch |
|
| installed. |
| is installed according to |
|
|
|
| manufacturer’s |
|
|
|
| instructions. |
| 3. | Defective flow switch. | 3. | Replace flow switch. |
| 4. | Remote cycling device open. | 4. | Check cycling devices |
|
|
|
| connected to terminals |
|
|
|
| 13 & 14 of the CTB1 |
|
|
|
| Terminal Block. |
|
|
|
| |
“LOW SUCTION PRESSURE” | 1. Improper suction pressure | 1. | Adjust per recommended | |
FAULT |
|
| settings. | |
| 2. | Low refrigerant charge. | 2. | Repair leak if necessary |
|
|
|
| and add refrigerant. |
| 3. | Fouled filter dryer. | 3. | Change dryer/core. |
|
|
|
| CONT’D |
|
|
|
|
|