FORM
PROBLEM |
| CAUSE | SOLUTION |
|
|
|
|
|
|
| |
“MP / HPCO” FAULT | 1. Compressor internal motor | 1. Verify refrigerant charge is |
|
| |
|
| protector (MP) open. | not low. Verify superheat |
|
|
|
|
| setting of ° 10 - 15° F (5.6° - |
|
|
|
|
| 8.3°C). Verify correct com- |
|
|
|
|
| pressor rotation. Verify |
|
|
|
|
| compressor is not over |
|
|
|
|
| loaded. |
|
|
| 2. | External overload tripped. | 2. Determine cause and reset. |
|
|
| 3. | HPCO switch open | 3. See “High Press. Disch.” |
|
|
|
|
| Fault |
|
|
| 4. | Defective HPCO switch | 4. Replace HPCO switch |
|
|
| 5. | Defective CR relay | 5. Replace relay |
|
|
|
|
|
|
| |
COMPRESSOR(S) WON’T | 1. Demand not great enough. | 1. No problem. Consult |
|
| |
| 3 | ||||
START |
|
| “Installation” Manual to aid |
| |
|
|
| in understanding compres- |
|
|
|
|
|
|
| |
|
|
| sor operation and capacity |
|
|
|
|
| control. |
|
|
| 2. | Defective water temperature | 2. Compare the display with a |
|
|
|
| sensor. | thermometer. Should be |
|
|
|
|
| within +/- 2 degrees. Refer |
|
|
|
|
| to Service section for RWT/ |
|
|
|
|
| LWT temp./voltage table. |
|
|
| 3. | Contactor/Overload failure | 3. Replace defective part. |
|
|
| 4. | Compressor failure | 4. Diagnose cause of failure |
|
|
|
|
| and replace. |
|
|
|
|
|
|
| |
LACK OF COOLING EFFECT | 1. Fouled evaporator surface. | 1. Contact the local YORK |
|
| |
|
| Low suction pressure will | service representative. |
|
|
|
| be observed. |
|
|
|
| 2. | Improper flow through the | 2. Reduce flow to within chiller |
|
|
|
| evaporator. | design specs. See Limita- |
|
|
|
|
| tions in Installation section. |
|
|
| 3. | Low refrigerant charge. | 3. Check subcooling and add |
|
|
|
| Low suction pressure will | charge as needed. |
|
|
|
| be observed. |
|
|
|
|
|
|
|
|
|
YORK INTERNATIONAL | 107 |