York YCAL0014SC, YCAL0080SC manual Service and Troubleshooting

Models: YCAL0080SC YCAL0014SC

1 136
Download 136 pages 36.22 Kb
Page 96
Image 96
Service and Troubleshooting

Service and Troubleshooting

SERVICE MODE - INPUTS

After entering the Service Mode, all digital and analog inputs to the microboard can be viewed by pressing the OPER DATA key. After pressing the OPER DATA key, the UP ARROW and DOWN ARROW keys are used to scroll through the analog and digital inputs.

Following is the order of analog and digital inputs that will appear when sequenced with the ARROW keys:

(analog inputs)

SYS 1 *SUCT PRESSURE

SYS 1 SPARE

SYS 1 **DISCH PRESSURE

SYS 1 SUCT TEMP (YCUL ONLY)

SYS 2 SUCT TEMP (YCUL ONLY)

SPARE

SPARE

AMBIENT AIR

LEAVING LIQUID

RETURN LIQUID

SYS 2 *SUCTION PRESSURE

SYS 2 SPARE

SYS 2 **DISCH PRESSURE

SYS 1 GRND FLT

SYS 2 GRND FLT

(binary inputs)

PWM TEMP RESET INPUT

LOAD LIMIT INPUT

FLOW SW / REM START

SYS 2 ZONE THERM (YCUL ONLY)

SINGLE SYSTEM SELECT

SYS 1 MP / HPCO INPUT

SYS 2 MP / HPCO INPUT

The analog inputs will display the input connection, the temperature or pressure, and corresponding input volt- age such as:

S Y S 1 S U C T

P R J 4 -

1 0

2 . 1 V D C =

8 1 P S I

G

 

 

 

This example indicates that the system 1 suction pres- sure input is connected to plug 4 - pin 10 (J4-10) on the microboard. It indicates that the voltage is 2.1 volts dc which corresponds to 81 PSIG (5.6 bars) suction pres- sure.

The digital inputs will display the input connection and ON/OFF status such as:

F L O W S W / R E M S T A R T

J 9 - 5 I S O N

This indicates that the flow switch/remote start input is connected to plug 9- pin 5 (J9-5) on the microboard, and is ON (ON = +30 VDC unregulated input, OFF = O VDC input on digital inputs).

CONTROL INPUTS/OUTPUTS

Tables 44 and 45 are a quick reference list providing the connection points and a description of the binary and analog inputs respectively. Table 46 lists the con- nection points for the outputs. All input and output con- nections pertain to the connections at the microboard.

Figure 8 illustrates the physical connections on the mi- croboard.

*The suction pressure transducer is optional on YCAL0014 - YCAL0060. A low pressure switch is standard on these models in place of the suction transducer.

**The discharge pressure transducer is optional on all models.

96

YORK INTERNATIONAL

Page 96
Image 96
York YCAL0014SC, YCAL0080SC manual Service and Troubleshooting