SERVICE AND TROUBLESHOOTING

FORM 150.62-NM1

SERVICE AND TROUBLESHOOTING

CLEARING HISTORY BUFFERS

The history buffers may be cleared by pressing the HIS- TORY key and then repeatedly pressing the UP arrow key until you scroll past the last history buffer choice. The following message will be displayed:

1 I N I T I A L I Z E

H

I S T O R Y

E N T E R =

Y E

S

 

 

 

Pressing the ENTER/ADV key at this display will cause the history buffers to be cleared. Pressing any other key will cancel the operation.

SOFTWARE VERSION

The software version may be viewed by pressing the HISTORY key and then repeatedly pressing the DOWN arrow key until you scroll past the first history buffer choice. The following message is an example of what will be displayed:

S O F T W A R E V E R S I O N

C . M M C . 0 1 . 0 1

SERVICE MODE

Service Mode is a mode that allows the user to view all the inputs to the microboard and enable or disable all of the outputs (except compressors) on the unit. Some in- ternal timers and counters will be viewable and modifi- able as well.

To enter Service Mode, turn the unit switch off and press the following keys in the sequence shown; PROGRAM, UP ARROW, UP ARROW, DOWN ARROW, DOWN ARROW, ENTER.

SERVICE MODE - DIGITAL OUTPUTS

After pressing the key sequence as described, the con- trol will enter the Service Mode permitting the digital out- puts (except compressors), operating hours, and start counters to be viewed/modified. The ENTER/ADV key is used to advance through the digital outputs. Using the UP/DOWN ARROW keys will turn the respective digital output on/off.

Following is the order of digital outputs that will appear as the ENTER/ADV key is pressed:\

SYS 1 COMPRESSOR 1

SYS 1 LIQUID LINE SOLENOID VALVE

SYS 1 COMPRESSOR 2

SYS 1 COMPRESSOR 3

SYS 1 HOT GAS BYPASS SOLENOID VALVE

SYS 2 COMPRESSOR 1

SYS 2 LIQUID LINE SOLENOID VALVE

SYS 2 COMPRESSOR 2

SYS 2 COMPRESSOR 3

SYS 1 FAN STAGE 1

SYS 1 FAN STAGE 2

SYS 1 FAN STAGE 3

SYS 2 FAN STAGE 1

SYS 2 FAN STAGE 2

SYS 2 FAN STAGE 3

EVAPORATOR HEATER

SYS 1 ALARM

SYS 2 ALARM

EVAPORATOR PUMP

SYS 1 & 2 ACCUM RUN TIME/STARTS

Each display will also show the output connection on the microboard for the respective digital output status shown. For example:

S Y S

1

L L S V

S T A T U S

T

B 3

- 2 I S

O F F

 

 

 

 

This display indicates that the system 1 liquid line sole- noid valve is OFF, and the output connection from the microboard is coming from terminal block 3 - pin 2.

Pressing the UP Arrow key will energize the liquid line solenoid valve and OFF will change to ON in the dis- play as the LLSV is energized.

The last display shown on the above list is for the accu- mulated run and start timers for each system. These values can also be changed using the UP and Down ARROW keys, but under normal circumstances would not be advised.

3

YORK INTERNATIONAL

95

Page 95
Image 95
York YCAL0080SC, YCAL0014SC manual Service And Troubleshooting, Clearing History Buffers, Software Version, Service Mode