York YCAL0014SC, YCAL0080SC manual Unit Controls, Operating Data Printout

Models: YCAL0080SC YCAL0014SC

1 136
Download 136 pages 36.22 Kb
Page 70
Image 70
OPERATING DATA PRINTOUT

Unit Controls

PRINT Key

The PRINT key allows the operator to obtain a printout of real-time system operating data or a printout of sys- tem data at the “instant of the fault” on the last six faults which occurred on the unit. An optional printer is re- quired for the printout.

OPERATING DATA PRINTOUT

Pressing the PRINT key and then OPER DATA key al- lows the operator to obtain a printout of current systemoperating parameters. When the OPER DATA key is pressed, a snapshot will be taken of system op- erating conditions and panel programming selections. This data will be temporarily stored in memory and trans- mission of this data will begin to the printer. A sample Oper Data printout is shown below.

YORK INTERNATIONAL CORPORATION

MILLENNIUM LIQUID CHILLER

UNIT STATUS

 

2:04PM 01 JAN 99

 

SYS 1

NO COOLING LOAD

SYS 2

COMPRESSORS RUNNING 2

 

OPTIONS

 

 

CHILLED LIQUID

 

WATER

AMBIENT CONTROL

STANDARD

LOCAL/REMOTE MODE

REMOTE

CONTROL MODE

LEAVING LIQUID

LEAD/LAG CONTROL

AUTOMATIC

FAN CONTROL

AMB & DSCH PRESS

PROGRAM VALUES

 

DSCH PRESS CUTOUT

395

PSIG

SUCT PRESS CUTOUT

44

PSIG

LOW AMBIENT CUTOUT

25.0

DEGF

LEAVING LIQUID CUTOUT

25.0

DEGF

ANTI RECYCLE TIME

600

SECS

FAN CONTROL ON PRESS

230

PSIG

FAN DIFF OFF PRESS

80

PSIG

NUMBER OF COMPRESSORS

 

6

 

UNIT DATA

 

RETURN LIQUID TEMP

58.2

DEGF

LEAVING LIQUID TEMP

53.0

DEGF

DISCHARGE AIR TEMP

55.3

DEGF

COOLING RANGE

42.0 +/- 2.0 DEGF

SYS 1 SETPOINT

70 +/- 3 PSIG

SYS 2 SETPOINT

70 +/-3 PSIG

AMBIENT AIR TEMP

74.8

DEGF

LEAD SYSTEM

 

 

SYS 2

EVAPORATOR PUMP

 

ON

EVAPORATOR HEATER

 

OFF

ACTIVE REMOTE CONTROL

 

NONE

SOFTWARE VERSION

C.M02.01.00

 

 

SYSTEM 1 DATA

COMPRESSORS STATUS

OFF

RUN

TIME

0- 0- 0- 0 D-H-M-S

SUCTION PRESSURE

66 PSIG

DISCHARGE PRESSURE

219 PSIG

SUCTION TEMPERATURE

52.8 DEGF

LIQUID LINE SOLENOID

OFF

HOT

GAS BYPASS VALVE

OFF

CONDENSER FAN STAGES

OFF

 

 

SYSTEM 2 DATA

COMPRESSORS STATUS

2

RUN

TIME

0- 0- 1-46 D-H-M-S

SUCTION PRESSURE

51 PSIG

DISCHARGE PRESSURE

157 PSIG

LIQUID LINE SOLENOID

ON

CONDENSER FAN STAGES

3

 

 

DAILY SCHEDULE

S M

T W T F S

*=HOLIDAY

MON

START=00:00AM

STOP=00:00AM

TUE

START=00:00AM

STOP=00:00AM

WED

START=00:00AM

STOP=00:00AM

THU

START=00:00AM

STOP=00:00AM

FRI

START=00:00AM

STOP=00:00AM

SAT

START=00:00AM

STOP=00:00AM

HOL

START=00:00AM

STOP=00:00AM

 

 

 

 

See Service And Troubleshooting sec- tion for Printer Installation informa- tion.

70

YORK INTERNATIONAL

Page 70
Image 70
York YCAL0014SC, YCAL0080SC manual Unit Controls, Operating Data Printout