York YCAL0014SC, YCAL0080SC manual Unit Controls

Models: YCAL0080SC YCAL0014SC

1 136
Download 136 pages 36.22 Kb
Page 86
Image 86
Manual background

Unit Controls

20sec. unloading

30sec. unloading

60sec. unloading

control range

(no compressor staging)

60sec. loading

LWT

42.5°F

43.5°F

44.0°F

46.0°F

48.0°

(5.8°C)

(6.4°C)

(6.7°C)

(7.8°C)

(8.9°C)

 

 

 

 

Low Limit

Setpoint

High limit

Leaving Water Temp. Control – Compressor Staging

Setpoint = 46.0°F (7.8°C) Range = +/- 2°F(1.1°C)

FIG. 6 – LEAVING WATER TEMPERATURE CONTROL

TABLE 32 – LEAVING CHILLED LIQUID CONTROL FOR 6 COMPRESSORS (8 STEPS)

 

LEAD SYSTEM

 

 

 

LAG SYSTEM

 

 

 

 

 

 

 

 

 

 

 

*STEP

COMP 1

COMP 2

COMP 3

 

COMP 1

 

COMP 2

 

COMP 3

0

OFF

OFF

OFF

 

OFF

 

OFF

 

OFF

1

ON+HG

OFF

OFF

SEE NOTE 1

OFF

 

OFF

 

OFF

2

ON

OFF

OFF

 

OFF

 

OFF

 

OFF

3

ON

OFF

OFF

SEE NOTE 2

ON

 

OFF

 

OFF

4

ON

ON

OFF

SEE NOTE 3

OFF

 

OFF

 

OFF

5

ON

ON

OFF

 

ON

 

OFF

 

OFF

6

ON

ON

OFF

 

ON

 

ON

 

OFF

7

ON

ON

ON

 

ON

 

ON

 

OFF

8

ON

ON

ON

 

ON

 

ON

 

ON

 

 

 

 

 

 

 

 

 

 

TABLE 33 – LEAVING CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)

 

LEAD SYSTEM

 

 

 

LAG SYSTEM

*STEP

COMP 1

COMP 2

 

COMP 1

 

COMP 2

0

OFF

OFF

 

OFF

 

OFF

1

ON+HG

OFF

SEE NOTE 1

OFF

 

OFF

2

ON

OFF

 

OFF

 

OFF

3

ON

OFF

SEE NOTE 2

ON

 

OFF

4

ON

ON

SEE NOTE 3

OFF

 

OFF

5

ON

ON

 

ON

 

OFF

6

ON

ON

 

ON

 

ON

* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.

86

YORK INTERNATIONAL

Page 86
Image 86
York YCAL0014SC, YCAL0080SC manual Unit Controls