Service and Troubleshooting
TABLE 53 – ISN TRANSMITTED DATA
ISN PAGE | TYPE | DATA | |
P42 | DIGITAL | SYS 1 LIQUID LINE SOLENOID | |
VALVE | |||
|
| ||
P43 | DIGITAL | SYS HOT GAS BYPASS VALVE | |
P44 | DIGITAL | — | |
P45 | DIGITAL | — | |
P46 | DIGITAL | SYS 2 LIQUID LINE SOLENOID | |
VALVE | |||
|
| ||
P47 | DIGITAL | LEAD SYSTEM (0=SYS 1, 1 SYS 2) | |
P48 | DIGITAL | — | |
P49 | DIGITAL | — | |
P50 | DIGITAL | CHILLED LIQUID TYPE | |
(0=WATER, 1=GLYCOL) | |||
|
| ||
P51 | DIGITAL | AMBIENT CONTROL MODE | |
(0=STD, 1 = AMB) | |||
|
| ||
P52 | DIGITAL | LOCAL / REMOTE CONTROL | |
MODE (0=LOCAL, 1=REMOTE) | |||
|
| ||
P53 | DIGITAL | UNITS (0=IMPERIAL, 1=SI) | |
P54 | DIGITAL | LEAD/LAG CONTROL MODE | |
(0=MANUAL, 1=AUTO) | |||
|
| ||
|
|
| |
P55 | DIGITAL | — | |
|
|
| |
P56 | CODED | *SYS 1 OPERATIONAL CODE | |
|
|
| |
P57 | CODED | *SYS 1 FAULT CODE | |
|
|
| |
P58 | CODED | *SYS 2 OPERATIONAL CODE | |
|
|
| |
P59 | CODED | *SYS 2 FAULT CODE | |
|
|
| |
P60 | CODED | SYS 1 COMP RUNNING | |
|
|
|
ISN PAGE | TYPE | DATA | |
P61 | CODED | SYS 1 COND FANS RUNNING | |
P62 | CODED | SYS 2 COMP RUNNING | |
P63 | CODED | SYS 2 COND FANS RUNNING | |
P64 | CODED | — | |
|
| UNIT CONTROL MODE | |
|
| 0=LEAVING WATER, | |
P65 | ANALOG | 1=RETURN WATER | |
|
| 2=DISCHARGE AIR, | |
|
| 3= SUCTION PRESSURE | |
P66 | ANALOG | ||
(PROGRAMMED) | |||
|
| ||
P67 | ANALOG | LEAVING CHILLED LIQUID | |
TEMP CUTOUT | |||
|
| ||
P68 | ANALOG | LOW AMBIENT TEMP CUTOUT | |
P69 | ANALOG | — | |
P70 | ANALOG | LOW SUCTION PRESS CUTOUT | |
P71 | ANALOG | HIGH DISCHARGE PRESS | |
CUTOUT | |||
|
| ||
P72 | ANALOG | SETPOINT | |
P73 | ANALOG | COOLING RANGE | |
P74 | ANALOG | SETPOINT 2 | |
(SP CONTROL) | |||
|
| ||
— | NO DATA | ||
ALL ZEROS | |||
|
| ||
|
|
|
*The operational and fault codes sent to pages 56 through 59 are defined in Table 54. Note that this table of fault and op codes is for all DX products. The codes that are grayed out are not used on this unit.
110 | YORK INTERNATIONAL |