CHECKING INPUTS AND OUTPUTS

CHECKING INPUTS AND OUTPUTS

BINARY INPUTS

Refer to the unit wiring diagram. All binary inputs are connected to J9 of the microboard. The term “binary” refers to two states –- either on or off. As an example, when the flow switch is closed, 30 volts dc will be ap- plied to J9, pin 5 (J9-5) of the microboard. If the flow switch is open, 0 volts dc will then be present at J9-5.

Pin 1 of J9 is an unregulated 30VDC that is the dc volt- age source used to supply the dc voltage to the various contacts, unit switch, flow switch, etc. This dc source is factory wired to CTB1, terminal 13. Any switch or con- tact used as a binary input would be connected to this terminal, with the other end connecting to it’s respective binary input on the microboard. Anytime a switch or con- tact is closed, 30VDC would be applied to that particular binary input. Anytime a switch or contact is open, 0VDC would be applied to that particular binary input.

Typically, as high as 34VDC could be measured for the dc voltage on the binary inputs. This voltage is in refer- ence to ground. The unit case should be sufficient as a reference point when measuring binary input voltages.

ANALOG INPUTS – Temperature

Refer to the unit wiring diagram. Temperature inputs are connected to the microboard on plug J6. These analog inputs represent varying dc signals corresponding to varying temperatures. All voltages are in reference to the unit case (ground). Following are the connections for the temperature sensing inputs:

Outside Air Sensor

J6-4 = +5VDC regulated supply to sensor.

J6-7 = VDC input signal to the microboard. See Table 47 for voltage readings that correspond to

specific outdoor temperatures.

J6-1 = drain (shield connection = 0VDC)

FORM 150.62-NM1

TABLE 47 – OUTDOOR AIR SENSOR TEMPERATURE/VOLTAGE/ RESISTANCE CORRELATION

TEMP °F

VOLTAGE

RESISTANCE

TEMP C°

0

0.7

85398

-18

 

 

 

 

5

0.8

72950

-15

 

 

 

 

10

0.9

62495

-12

15

1.0

53685

-9

 

 

 

 

20

1.1

46240

-7

 

 

 

 

25

1.2

39929

-4

30

1.4

34565

-1

 

 

 

 

35

1.5

29998

2

 

 

 

 

40

1.7

26099

4

45

1.8

22673

7

 

 

 

 

50

2.0

19900

10

 

 

 

 

55

2.2

17453

13

60

2.3

15309

16

 

 

 

 

65

2.5

13472

18

 

 

 

 

70

2.6

11881

21

75

2.8

10501

24

 

 

 

 

80

2.9

9298

27

 

 

 

 

85

3.1

8250

29

90

3.2

7332

32

 

 

 

 

95

3.4

6530

35

 

 

 

 

100

3.5

5827

38

105

3.6

5209

41

 

 

 

 

110

3.7

4665

43

 

 

 

 

115

3.8

4184

46

120

3.9

3759

49

 

 

 

 

125

4.0

3382

52

 

 

 

 

130

4.1

3048

54

3