“UNIT” KEYS

FORM 150.62-NM1

“UNIT” KEYS

OPTIONS key

There are eleven programmable options (nine for units with a single refrigerant system) under the OPTIONS key. The OPTIONS key is used to scroll through the list of options by repeatedly pressing the OPTIONS key . After the selected option has been displayed, the UP and DOWN arrow keys are then used to change that particular option. After the option is changed, the EN- TER/ADV key must be pressed to enter the data into memory. Table 31 shows the programmable options. Following are the displays in the order they appear:

Option 1 – Language

D I S P L A Y L A N G U A G E

E N G L I S H

Option 2 – System Switches (two system units only)

S Y S

1

S W I

T C H

O N

S Y S

2

S W I

T C H

O N

 

 

 

 

 

This allows both systems to run

or

S Y S

1

S W I

T C H

O N

S Y S

2

S W I

T C H

O F F

 

 

 

 

 

2

00070VIP

This keeps system 2 off

or

S Y S

1

S W I

T C H

O F F

S Y S

2

S W I

T C H

O N

 

 

 

 

 

This keeps system 1 off

Option 3 – Unit Type

U N I T T Y P E

L I Q U I D C H I L L E R

selected for YCAL Chillers

or

U N I T T Y P E

C O N D E N S I N G U N I T

selected for YCUL Condensing units.

Option 4 – Chilled Liquid Cooling Type

C H I L L E D L I Q U I D

W A T E R

The chilled liquid is water. The Cooling Setpoint can be programmed from 40°F to 70°F (4.4°C to 21.1°C)