OPERATIONAL LIMITATIONS (METRIC)

OPERATIONAL LIMITATIONS (METRIC)

TABLE 11 – TEMPERATURES AND FLOWS

 

 

LEAVING WATER

COOLER FLOW (L/S)

AIR ON CONDENSER (°C)

YCAL00

TEMPERATURE (°C)

 

 

 

 

 

 

MIN1

MAX2

MIN

MAX

MIN4

MAX5

14SC

4.4

12.8

1.9

3.8

-3.9

51.7

20SC

4.4

12.8

1.9

3.8

-3.9

51.7

24SC

4.4

12.8

2.2

4.4

-3.9

51.7

30SC

4.4

12.8

2.8

4.7

-3.9

51.7

34SC

4.4

12.8

4.7

6.9

-3.9

51.7

40SC

4.4

12.8

4.7

15.8

-3.9

51.7

44SC

4.4

12.8

4.7

15.8

-3.9

51.7

50SC

4.4

12.8

4.7

15.8

-3.9

51.7

60SC

4.4

12.8

4.7

15.8

-3.9

51.7

64SC

4.4

12.8

8.2

24.6

-3.9

51.7

70SC

4.4

12.8

8.2

24.6

-3.9

51.7

74SC

4.4

12.8

8.2

24.6

-3.9

51.7

80SC

4.4

12.8

7.6

27.1

-3.9

51.7

VOLTAGE LIMITATIONS

The following voltage limitations are absolute and op- eration beyond these limitations may cause serious damage to the compressor.

TABLE 12 – VOLTAGES

UNIT POWER

MIN.

MAX.

200-3-60

180

220

230-3-60

207

253

380-3-60

355

415

460-3-60

414

506

575-3-60

517

633

NOTES:

Excessive flow will cause damage to the cooler. Do not exceed max. cooler flow. Special care should be taken when multiple chillers are fed by a single pump.

1.Standard units cannot be operated below 4.4°C leaving chilled water temperature.

2.For leaving water temperature higher than 12.8°C, contact the nearest YORK Office for application guidelines.

3.The evaporator is protected against freeze-up to -28.9°C with an electrical heater as standard.

4.Operation below -3.9°C requires Optional Low Ambient Kit for operation to -17.8 °C.

5.Operation above 46.1°C requires Optional High Ambient Kit for operation to 51.7°C.