EMS-PWM REMOTE TEMPERATURE RESET
A contact closure on the PWM Temp Reset input at CTB 1 terminals 13 - 20, will reset the chilled liquid setpoint based on the length of time the contacts re- main closed. The maximum temperature reset is achieved at a contact closure of 11 seconds. This is the longest contact closure time allowed. One second is the shortest time allowed and causes the Chilled Liquid Setpoint to revert back to the Local programmed value. The reset value is always added to the Chilled Liquid Setpoint, meaning that this function never lowers the Chilled Liquid Setpoint below the locally programmed value, it can only reset to a higher value. The micro- board must be refreshed between 30 seconds and 30 minutes. Any contact closure occurring sooner than 30 seconds will be ignored. If more than 30 minutes elapse before the next contact closure, the setpoint will revert back to the locally programmed value. The new chilled liquid setpoint is calculated by the following equations:
setpoint = local chilled liquid setpoint + °reset °reset = (Contact Closure - 1) x (*Max. Reset Value)
10
Example:
Local Chilled Liquid Setpoint = 45°F (7.22°C). *Max Reset Value = 10°F (5.56°C)
Contact Closure Time = 6 Seconds.
(English)
(6 sec. - 1) (10°F/10) = 5°F Reset
So...the new chilled liquid setpoint = 45°F + 5°F= 50°F. This can be viewed by pressing the Cooling Setpoints key twice. The new value will be displayed as “REM SETP = 50.0°F.”
(Metric)
(6 sec - 1) * (5.56°C/10) = 2.78°C
Reset Cooling Setpoint = 7.22°C + 2.78°C = 10.0°C
So...the new reset Cooling Setpoint = 7.22 °C + 2.78°C = 10°C. This can be viewed by pressing the Cooling Setpoints key twice. The new value will be displayed as “REM SETP = 10.0°C.”
FORM
BAS/EMS TEMPERATURE RESET OPTION
The Remote Reset Option allows the Control Center of the unit to reset the chilled liquid setpoint using a 0 - 10 VDC input, a
The optional Remote Reset option would be used when reset of the chilled liquid setpoint is required and a PWM signal (timed contact closure) cannot be supplied by an Energy Management System. The Remote Temp. Re- set Board will convert a voltage, current, or contact sig- nal that is available from an EMS to a PWM signal, and every 80 seconds provide a PWM input to the micro- board. Figure 3 shows a diagram of the field and fac- tory electrical connections.
If a 0 - 10VDC signal is available, it is applied to termi- nals A+ and
setpoint = local chilled liquid setpoint + °reset
°reset = (dc voltage signal) x (*Max Reset Value) 10
Example:
Local Chilled Liquid Setpoint = 45°F (7.22°C)
*Max Reset Value = 20°F (11.11°C)
Input Signal = 6 VDC
(English)
°reset = 6VDC x 20°F = 12° F reset 10
setpoint = 45 °F + 12 °F = 57°F
(Metric)
°reset = 6VDC x 11. 11°C = 6.67°C reset 10
setpoint = 7.22°C + 6.67°C = 13.89°C
2
*Max Reset Value is the “Max
YORK INTERNATIONAL | 93 |