York YCAL0014SC, YCAL0080SC Unit Controls, Evaporator Pump Control, Evaporator Heater Control

Models: YCAL0080SC YCAL0014SC

1 136
Download 136 pages 36.22 Kb
Page 90
Image 90
EVAPORATOR PUMP CONTROL

Unit Controls

EVAPORATOR PUMP CONTROL

The evaporator pump dry contacts (CTB2 - terminals 23 - 24) are energized when any of the following condi- tions are true:

1.Low Leaving Chilled Liquid Fault

2.Any compressor is running

3.Daily Schedule is not programmed OFF and Unit Switch is ON.

The pump will not run if the micro panel has been pow- ered up for less than 30 seconds or if the pump has run in the last 30 seconds to prevent pump motor overheat- ing.

EVAPORATOR HEATER CONTROL

The evaporator heater is controlled by ambient air tem- perature. When the ambient temperature drops below 40°F (4.4°C) the heater is turned on. When the tem- perature rises above 45°F (7.2°C) the heater is turned off. An under voltage condition will keep the heater off until full voltage is restored to the system.

CONDENSER FAN CONTROL

Condenser fan operation must be programmed with the Options key under “Fan Control.” Condenser fan con- trol can be selected for Ambient Temp. and Disch. Pres- sure, or Discharge Pressure Only.

The condenser fan control by “Ambient Temperature and Discharge Pressure” is a feature that is integral to the standard software control. If the optional discharge transducer is not installed, the condenser fans will op- erate based on outdoor ambient temperature only. See Table 39.

The condenser fan control by “Discharge Pressure” is a feature that can be selected if the discharge pressure transducer is installed and fan recycling is not a con- cern. Fan control by discharge pressure will work ac- cording to Table 40. The fan control on-pressure (ctrl_press) and fan differential off-pressure (diff_press) are programmable under the PROGRAM key.

TABLE 39 – CONDENSER FAN CONTROL USING OUTDOOR AMBIENT TEMPERATURE AND DISCHARGE PRESSURE

FAN STAGE

ON

OFF

1

OAT >25° F (-3.9°C)

OAT < 20° F (-6.7°C)

OR

AND

1 FAN FWD

DP > ctrl_press

DP < ctrl_press - diff_press

 

2

OAT >45° F (7.2°C)

OAT < 40° F (4.4°C)

OR

AND

2 FANS FWD

DP > ctrl_press + 20 PSIG (1.38 Bars)

DP < ctrl_press - diff_press + 20 PSIG (1.38 Bars)

 

 

 

 

TABLE 40 – CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY

FAN STAGE

ON

OFF

1

DP > ctrl_press

DP < ctrl_press - diff_press

1 FAN FWD

 

 

2

DP > ctrl_press + 20 PSIG

(1.38 Bars) DP < ctrl_press - diff_press + 20 PSIG (1.38 Bars)

2 FANS FWD

 

 

90

YORK INTERNATIONAL

Page 90
Image 90
York YCAL0014SC, YCAL0080SC manual Unit Controls, Evaporator Pump Control, Evaporator Heater Control, Condenser Fan Control