Unit Controls
or
C H I L L E D L I Q U I D
G L Y C O L
The chilled liquid is glycol. The Cooling Setpoint can be programmed from 10°F to 70°F
Option 5 – Ambient Control Type
A M B I E N T C O N T R O L
S T A N D A R D
The low ambient cutout is adjustable from 25°F to 60°F
or
A M B I E N T C O N T R O L
L O W A M B I E N T
The low ambient cutout is programmable down to 0°F
Option 6 – Local/Remote Control Type
L O C A L / R E M O T E M O D E L
L O C A L
When programmed for LOCAL, an ISN or RCC control can be used to monitor only. The micro panel will oper-
ate on locally programmed values and ignore all com- mands from the remote devices. The chiller will com- municate and send data to the remote monitoring de- vices.
or
L O C A L / R E M O T E M O D E
R E M O T E
This mode should be selected when an ISN or RCC control is to be used to control the chiller. This mode will allow the ISN to control the following items: Remote Start/Stop, Cooling Setpoint, Load Limit, and History Buffer Request. If the unit receives no valid ISN trans- mission for 5 minutes, it will revert back to the locally programmed values.
Option 7 – Unit Control Mode
C O N T R O L M O D E
R E T U R N L I Q U I D
Unit control is based on return chilled liquid temp. It can only be selected on units that have 4 or 6 compressors (dual system units).
or
C O N T R O L M O D E
L E A V I N G L I Q U I D
Unit control is based on leaving chilled liquid temp.
Refer to section on Capacity Control for details on load- ing and unloading sequences.
82 | YORK INTERNATIONAL |