LOW AMBIENT CONDENSER FAN CONTROL
For unit operation below 25°F
With the low ambient kit installed and the unit pro- grammed for low ambient operation, the condenser fans will operate as shown in Tables 41 and 42.
FORM
Again, notice that condenser fan operation can be pro- grammed for either “temperature and discharge pres- sure control,” or “discharge pressure control only” as described under Condenser Fan Control.
The fan control
TABLE 41 – LOW AMBIENT CONDENSER FAN CONTROL – AMBIENT TEMPERATURE AND DISCHARGE PRESSURE CONTROL
FAN STAGE |
| ON | OFF | |
1 | OAT >25° F | OAT < 20° F | ||
| OR | AND | ||
1 FAN REV |
| |||
DP > ctrl_press | DP < ctrl_press - diff_press | |||
| ||||
2 | OAT >45°F (7.2°C) | OAT < 40°F | ||
| OR | AND | ||
1 FAN FWD |
| |||
DP > ctrl_press | + 20 PSIG (1.38 Bars) | DP < ctrl_press - diff_press + 20 PSIG (1.38 Bars) | ||
| ||||
|
|
| ||
3 | OAT > 65°F (18.3°C) | OAT < 60°F (15.6°C) | ||
| OR | AND | ||
2 FANS FWD |
| |||
DP > ctrl_press + 40 PSIG (2.76 Bars) | DP < ctrl_press - diff_press + 40 PSIG (2.76 Bars) | |||
| ||||
|
|
|
|
2
TABLE 42 – LOW AMBIENT CONDENSER FAN CONTROL – DISCHARGE PRESSURE CONTROL
FAN STAGE | ON |
| OFF |
1 |
|
|
|
1 FAN REV | DP > ctrl_press | DP < ctrl_press - diff_press | |
2 |
|
|
|
1 FAN FWD | DP > ctrl_press + 20 | PSIG (1.38 Bars) | DP < ctrl_press - diff_press + 20 PSIG (1.38 Bars) |
|
|
|
|
3 |
|
|
|
2 FANS FWD | DP > ctrl_press + 40 | PSIG (2.76 Bars) | DP < ctrl_press - diff_press + 40 PSIG (2.76 Bars) |
|
|
|
|
YORK INTERNATIONAL | 91 |