Unit Controls
U N I T F A U L T :
L O W A M B I E N T T E M P
The Low Ambient Temp Cutout is a safety shutdown designed to protect the chiller from operating in a low ambient condition. If the outdoor ambient temperature falls below the programmable cutout, the chiller will shut down. Restart can occur when temperature rises 2°F above the cutoff.
U N I T F A U L T :
L O W L I Q U I D T E M P
The Low Leaving Chilled Liquid Temp Cutout protects the chiller form an evaporator
U N I T F A U L T :
1 1 5 V A C U N D E R V O L T A G E
The Under Voltage Safety assures that the system is not operated at voltages where malfunction of the mi- croprocessor could result in system damage. When the115VAC to the micro panel drops below a certain level, a unit fault is initiated to safely shut down the unit.
Restart is allowed after the unit is fully powered again and the
UNIT WARNING
The following message is not a unit safety and will not be logged to the history buffer. It is a unit warning and will not
! ! L O W B A T T E R Y | ! ! |
C H E C K P R O G / S E T P | / O P T N |
|
|
The Low Battery Warning can only occur at unit power- up. On micro panel
If a low battery is detected, it should be replaced as soon as possible. The programmed values will all be lost and the unit will be prevented from running on the next power interruption. The RTC/battery is located at U17 on the microboard.
64 | YORK INTERNATIONAL |