Compressor Staging for Return Water Control –

FORM 150.62-NM1

Compressor Staging for Return Water Control –

6 Compressors

Cooling Setpoint = 45° F (7.2° C) Range = 10° F (5.6° C)

TABLE 36 – COMPRESSOR STAGING FOR RETURN WATER CONTROL

# OF COMP ON

0

*1+HG

1

2

3

4

5

6

RWT

45°F

46.25°F

46.7°F

48.3°F

50.0°F

51.7°F

53.4°F

55.0°F

(7.2°C)

(7.9°C)

(8.2°C)

(9.1°C)

(10.0°C)

(11.0°C)

(11.9°C)

(12.8°C)

 

 

 

 

 

 

 

 

 

 

*Unloading only

TABLE 37 – RETURN CHILLED LIQUID CONTROL FOR 6 COMPRESSORS (8 STEPS)

*STEP

COMPRESSOR ON POINT

COMPRESSOR OFF POINT

 

0

 

 

 

1

 

SETPOINT

 

 

 

 

 

2

SP + CR/6

SP + CR/8

SEE NOTE 1

3

SP + 2*CR/6

SP + CR/6

SEE NOTE 2

4

SP + 2*CR/6

SP + CR/6

SEE NOTE 3

 

 

 

 

5

SP + 3*CR/6

SP + 2*CR/6

 

6

SP + 4*CR/6

SP + 3*CR/6

 

7

SP + 5*CR/6

SP + 4*CR/6

 

 

 

 

 

8

SP + CR

SP + 5*CR/6

 

2

TABLE 38 – RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)

*STEP

COMPRESSOR ON POINT

COMPRESSOR OFF POINT

 

0

 

 

 

1

 

SETPOINT

 

 

 

 

 

2

SP + CR/4

SP + CR/8

SEE NOTE 1

3

SP + 2*CR/4

SP + CR/4

SEE NOTE 2

4

SP + 2*CR/4

SP + CR/4

SEE NOTE 3

 

 

 

 

5

SP + 3*CR/4

SP + 2*CR/4

 

6

SP + CR

SP + 3*CR/4

 

 

 

 

 

Notes:

1.Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown.

2.Step 3 is skipped when loading occurs.

3.Step 4 is skipped when unloading occurs.

* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.