York YCAL0080SC, YCAL0014SC manual Compressor Staging for Return Water Control, Compressors

Models: YCAL0080SC YCAL0014SC

1 136
Download 136 pages 36.22 Kb
Page 89
Image 89
Compressor Staging for Return Water Control –

FORM 150.62-NM1

Compressor Staging for Return Water Control –

6 Compressors

Cooling Setpoint = 45° F (7.2° C) Range = 10° F (5.6° C)

TABLE 36 – COMPRESSOR STAGING FOR RETURN WATER CONTROL

# OF COMP ON

0

*1+HG

1

2

3

4

5

6

RWT

45°F

46.25°F

46.7°F

48.3°F

50.0°F

51.7°F

53.4°F

55.0°F

(7.2°C)

(7.9°C)

(8.2°C)

(9.1°C)

(10.0°C)

(11.0°C)

(11.9°C)

(12.8°C)

 

 

 

 

 

 

 

 

 

 

*Unloading only

TABLE 37 – RETURN CHILLED LIQUID CONTROL FOR 6 COMPRESSORS (8 STEPS)

*STEP

COMPRESSOR ON POINT

COMPRESSOR OFF POINT

 

0

 

 

 

1

 

SETPOINT

 

 

 

 

 

2

SP + CR/6

SP + CR/8

SEE NOTE 1

3

SP + 2*CR/6

SP + CR/6

SEE NOTE 2

4

SP + 2*CR/6

SP + CR/6

SEE NOTE 3

 

 

 

 

5

SP + 3*CR/6

SP + 2*CR/6

 

6

SP + 4*CR/6

SP + 3*CR/6

 

7

SP + 5*CR/6

SP + 4*CR/6

 

 

 

 

 

8

SP + CR

SP + 5*CR/6

 

2

TABLE 38 – RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)

*STEP

COMPRESSOR ON POINT

COMPRESSOR OFF POINT

 

0

 

 

 

1

 

SETPOINT

 

 

 

 

 

2

SP + CR/4

SP + CR/8

SEE NOTE 1

3

SP + 2*CR/4

SP + CR/4

SEE NOTE 2

4

SP + 2*CR/4

SP + CR/4

SEE NOTE 3

 

 

 

 

5

SP + 3*CR/4

SP + 2*CR/4

 

6

SP + CR

SP + 3*CR/4

 

 

 

 

 

Notes:

1.Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown.

2.Step 3 is skipped when loading occurs.

3.Step 4 is skipped when unloading occurs.

* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.

YORK INTERNATIONAL

89

Page 89
Image 89
York YCAL0080SC Compressor Staging for Return Water Control, Compressors, Cooling Setpoint = 45 F 7.2 C Range = 10 F 5.6 C