York YCAL0080SC, YCAL0014SC manual Unit Operation, Capacity Control, Leaving Chilled Liquid Control

Models: YCAL0080SC YCAL0014SC

1 136
Download 136 pages 36.22 Kb
Page 85
Image 85
UNIT OPERATION

FORM 150.62-NM1

UNIT OPERATION

CAPACITY CONTROL

To initiate the start sequence of the chiller, all run per- missive inputs must be satisfied (flow/remote start/stop switch), and no chiller or system faults exist.

The first phase of the start sequence is initiated by the Daily Schedule Start or a Remote Cycling Device. If the unit is shut down on the daily schedule, the chilled wa- ter pump microboard contacts (TB5 3-4) will close when the daily schedule start time has been reached. Once flow has been established and the flow switch closes, capacity control functions are initiated.

If unit cycling is accomplished with a remote cycling device wired in series with the flow switch, the chilled water pump contacts will always be energized as long as the unit switch is turned on. When the flow switch and remote cycling contacts are closed, the capacity control functions will be initiated.

It should be noted that the chilled water pump contacts (TB5 3-4) are not required to be used to cycle the chilled water pump. However, in all cases the flow switch must be closed to allow unit operation.

The control system will evaluate the need for cooling by comparing the actual leaving or return chilled liquid tem- perature to the desired setpoint, and regulate the leav- ing or return chilled liquid temperature to meet that de- sired setpoint.

LEAVING CHILLED LIQUID CONTROL

The setpoint, when programmed for Leaving Chilled Liq- uid Control, is the temperature the unit will control to within +/- the cooling range. The Setpoint High Limit is the Setpoint plus the Cooling Range. The Setpoint Low Limit is the Setpoint minus the Cooling Range. See Fig- ure 6.

If the leaving chilled liquid temperature is above the Setpoint High Limit, the lead compressor on the lead system will be energized along with the liquid line sole- noid. Upon energizing any compressor, the 60 second Anti-Coincidence timer will be initiated.

If after 60 seconds of run-time the leaving chilled liquid temperature is still above the Setpoint High Limit, the next compressor in sequence will be energized. Addi- tional loading stages are energized at a rate of once every 60 seconds if the chilled liquid temperature re- mains above the Setpoint High Limit. In this case, the load timer will be 60 seconds.

If the chilled liquid temperature falls below the Setpoint High Limit but is greater than the Setpoint Low Limit, loading and unloading do not occur. This area of con- trol is called the control range.

If the chilled liquid temperature drops to less than 0.5°F (.28°C) below the Setpoint Low Limit, unloading occurs at a rate of 60 seconds. If the chilled liquid temperature falls to a value greater than 0.5°F (.28°C) below the Setpoint Low Limit but not greater than 1.5°F (.83°C) below the Setpoint Low Limit, unloading occurs at a rate of 30 seconds. If the chilled liquid temperature falls to a value greater than 1.5°F (.83°C) below the Setpoint Low Limit, unloading occurs at a rate of 20 seconds.

The leaving chilled liquid setpoint is programmable from 40°F to 70°F (4.4°C to 21.1°C) in water chilling mode and from 10°F to 70°F (-12.2°C to 21.1°C) in glycol chill- ing mode. In both modes, the cooling range can be from +/-1.5°F to +/-2.5°F (+/-.83°C to 1.39°C).

The sequences of Capacity Control (compressor stag- ing) for loading and unloading are shown in Table 32 through Table 35.

2

YORK INTERNATIONAL

85

Page 85
Image 85
York YCAL0080SC, YCAL0014SC manual Unit Operation, Capacity Control, Leaving Chilled Liquid Control