ISN CONTROL

FORM 150.62-NM1

ISN CONTROL

RECEIVED DATA (CONTROL DATA)

The Middle Market receives 8 data values from the ISN. The first 4 are analog values and the last 4 are digital values. These 8 data values are used as control pa- rameters when in REMOTE mode. When the unit is in LOCAL mode, these 8 values are ignored. If the unit receives no valid ISN transmission for 5 minutes it will revert back to all local control values. Table 51 lists the 5 control parameters. These values are found under feature 54 on the ISN.

TABLE 51 – ISN RECEIVED DATA

ISN PAGE

CONTROL DATA

 

 

P03

SETPOINT

P04

LOAD LIMIT STAGE (0,1, 2)

P05

COOLING RANGE (DAT MODE ONLY)

P06

P07

START/STOP COMMAND

P08

P09

P10

HISTORY BUFFER REQUEST

TRANSMITTED DATA

After receiving a valid transmission from the ISN, the unit will transmit either operational data or history buffer data depending on the “History Buffer Request” in page

10.Data must be transmitted for every ISN page under feature 54. If there is no value to be sent to a particular page, a zero will be sent. Tables 52 - 53 show the data values and page listings for this unit.

TABLE 52 – ISN TRANSMITTED DATA

ISN PAGE

TYPE

DATA

P11

ANALOG

LEAVING CHILLED LIQUID TEMP.

P12

ANALOG

RETURN CHILLED LIQUID TEMP.

P13

ANALOG

MIXED CHILLED LIQUID TEMP.

P14

ANALOG

DISCHARGE AIR TEMP.

P15

ANALOG

P16

ANALOG

AMBIENT AIR TEMP.

P17

ANALOG

P18

ANALOG

SYS 1 RUN TIME (SECONDS)

P20

ANALOG

SYS 1 DISCHARGE PRESSURE

P21

ANALOG

P22

ANALOG

P23

ANALOG

P24

ANALOG

SYS 1 ANTI-RECYCLE TIMER

P25

ANALOG

ANTI-COINCIDENT TIMER

P27

ANALOG

SYS 2 RUN TIME (SECONDS)

P28

ANALOG

SYS 2 SUCTION PRESSURE

P29

ANALOG

SYS 2 DISCHARGE PRESSURE

P33

ANALOG

SYS 2 ANTI-RECYCLE TIMER

P35

ANALOG

NUMBER OF COMPRESSORS

P36

DIGITAL

SYS 1 ALARM

P37

DIGITAL

SYS 2 ALARM

P38

DIGITAL

EVAPORATOR HEATER STATUS

P39

DIGITAL

EVAPORATOR PUMP STATUS

P40

DIGITAL

P41

DIGITAL

 

 

 

3

YORK INTERNATIONAL

109