DIMENSIONS (ENGLISH)

Installation

DIMENSIONS (ENGLISH)

YCAL0014SC - YCAL0020SC

LD03848

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended mini- mum clearances: Side to wall – 6'; rear to wall– 6'; control panel to end wall– 4'0; top– no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.