“STATUS” KEY

Unit Controls

“STATUS” KEY

00066VIP

The following messages are displayed when the “Sta- tus” key is pressed. Following each displayed message is an explanation pertaining to that particular display.

GENERAL STATUS MESSAGES

In the case of messages which apply to individual sys- tems, SYS 1 and, SYS 2 messages will both be dis- played and may be different. In the case of single sys- tem units, all SYS 2 messages will be blank.

U N I T S W I T C H O F F

S H U T D O W N

This message informs the operator that the UNIT switch on the control panel is in the OFF position which will not allow the unit to run.

R E M O T E C O N T R O L L E D

S H U T D O W N

The REMOTE CONTROLLED SHUTDOWN message indicates that either an ISN or BAS system has turned the unit off, not allowing it to run.

D A I L Y S C H E D U L E

S H U T D O W N

The DAILY SCHEDULE SHUTDOWN message indi- cates that the daily/holiday schedule programmed is keeping the unit from running.

F L O W S W I T C H / R E M S T O P

N O R U N P E R M I S S I V E

NO RUN PERM shows that either the flow switch is open or a remote start/stop contact is open in series with the flow switch.

60

YORK INTERNATIONAL

Page 60
Image 60