Unit Controls
+ |
– |
LD03875 |
FIG. 7 – FIELD AND FACTORY ELECTRICAL CONNECTIONS
OPTIONAL REMOTE TEMPERATURE RESET BOARD
If a
setpoint = local chilled liquid setpoint + °reset
°reset = (mA signal - 4) x (*Max Reset Value) 16
Example:
Local Chilled Liquid Setpoint = 45° (7.22°C)
*Max Reset Value = 10°F (5.56°C)
Input Signal = 12 mA
(English)
°reset = 8mA x 10°F = 5°F reset 16
setpoint = 45°F + 5°F = 50°F
(Metric)
°reset = 8mA x 5.56°C = 2.78°C reset 16
setpoint = 7.22°C + 2.78°C = 10.0°C
A
If the Contact Closure input is used. The connections are made to terminals C and D and only jumper JUI must be in place on the reset board. This input is used when a single reset value is needed. When the contacts are closed, the remote temperature reset board will con- vert this contact closure to a PWM signal that is applied to CTB 1 terminals 13 - 20.
To set the PWM output, the contacts must be closed on inputs C - D, and potentiometer R11 (located on the front edge of the PC board) is adjusted to 10VDC as mea- sured at TP3 to terminal 10 on the circuit board. The reset value will be the “Max
NOTE: The coil of any added relay used for reset must be suppressed to prevent possible component damage. Use YORK
*Max Reset Value is the “Max