TABLE 29 – PROGRAM KEY LIMITS AND DEFAULTS

FORM 150.62-NM1

Another anti-recycle timer is started each time the sys- tems number one compressor cycles off. This anti-re- cycle time is fixed at 120 seconds and starts to count- down when the systems number one compressor cycles off.

The anti-recycle message is displayed when the sys- tem is unable to start due to either of the anti-recycle timers being active (counting down). The actual time displayed will be the longer of the two timers, start-to- start or stop-to-start.

F A N C O N T R O L O N

P R E S S U R E = X X X P S I G

The Fan Control On Pressure is the programmed pres- sure value that is used to stage the condenser fans on, in relation to discharge pressure. Refer to Condenser Fan Control in the UNIT OPERATION section and Tables 38, 39, and 40, 41.

TABLE 29 – PROGRAM KEY LIMITS AND DEFAULTS

F A N D I F F E R E N T I A L O F F P R E S S U R E = X X X P S I G

The Fan Differential Off Pressure is the programmed differential pressure value that is used to stage the con- denser fans off, in relation to discharge pressure. Refer to Condenser Fan Control in the UNIT OPERATION section and Tables 38, 39 and 40, 41.

T O T A L N U M B E R O F

C O M P R E S S O R S = 6

The TOTAL NUMBER OF COMPRESSORS are the amount of compressors in the chiller, and determines the stages of cooling available. Notice in Table 29 the chiller is a single or dual refrigerant circuit.

This must be programmed correctly to assure proper chiller operation.

2

PROGRAM VALUE

MODEL

LOW LIMIT

HIGH LIMIT

DEFAULT

DISCHARGE PRESSURE CUTOUT

200 PSIG

399 PSIG

395 PSIG

13.8 BARS

27.5 BARS

27.2 BARS

 

 

 

 

 

 

 

 

WATER COOLING

44.0 PSIG

70.0 PSIG

44.0 PSIG

 

3.03 BARS

4.83 BARS

3.03 BARS

SUCTION PRESSURE CUTOUT

 

GLYCOL COOLING

20.0 PSIG

70.0 PSIG

44.0 PSIG

 

 

1.38 BARS

4.83 BARS

3.03 BAR

 

 

 

STANDARD AMBIENT

25.0°F

60.0°F

25.0°F

 

-3.9°C

15.6°C

-3.9°C

LOW AMBIENT TEMP. CUTOUT

 

LOW AMBIENT

0°F

60.0°F

25.0°F

 

 

-17.8°C

15.6°C

-3.9°C

 

 

 

WATER COOLING

36°F

LEAVING CHILLED LIQUID

2.2°C

 

 

 

 

 

 

 

 

TEMP. CUTOUT

GLYCOL COOLING

8.0°F

36.0°F

36.0°F

 

-13.3°C

2.2°C

2.2°C

 

 

ANTI-RECYCLE TIMER

300 SEC.

600 SEC.

600 SEC.

FAN CONTROL ON-PRESSURE

225 PSIG

300 PSIG

230 PSIG

15.5 BARS

20.7 BARS

15.9 BARS

 

 

FAN DIFFERENTIAL OFF-PRESSURE

50 PSIG

150 PSIG

80 PSIG

3.45 BARS

10.3 BARS

5.52 BARS

 

 

 

 

 

 

 

TOTAL NUMBER OF COMPRESSORS

SINGLE SYSTEM

2

3

3

TWO SYSTEMS

4

6

6

 

 

 

 

 

 